Use Of Ansi C-Class Cts - GE P24DM Technical Manual

Motor protection ied
Table of Contents

Advertisement

P24xM
Secondary Internal Fault Current
50A
100A
150A
In some situations single disc assemblies may be acceptable, contact General Electric for detailed applications.
Note:
The Metrosils recommended for use with 5 Amp CTs can also be used with triple pole devices and consist of three single pole
units mounted on the same central stud but electrically insulated from each other. To order these units please specify "Triple
pole Metrosil type", followed by the single pole type reference. Metrosil for higher voltage settings and fault currents are
available if required.
2.8

USE OF ANSI C-CLASS CTS

Where American/IEEE standards are used to specify CTs, the C class voltage rating can be used to determine the
equivalent knee point voltage according to IEC. The equivalence formula is:
=
1 05
. (
V
C rating in volts
K
P24xM-TM-EN-2.1
Recommended Metrosil types for various voltage settings
600A/S1/S1213
600A/S1/S1214
C = 540/640
C = 670/800
35 mA RMS
40 mA RMS
600A/S2/P/
600A/S2/P/S1215
S1217
C = 570/670
C = 470/540
75 mA RMS
70 mA RMS
600A/S3/P/
600A/S3/P/S1220
S1219
C = 520/620
C = 430/500
100 mA RMS
100 mA RMS
)
+
100
R
CT
Chapter 9 - Current Transformer Requirements
600A/S1/S1214
C =670/800
50 mA RMS
600A/S2/P/S1215
C =570/670
100 mA RMS
600A/S3/P/S1221
C = 570/670
100 mA RMS
600A/S1/S1223
C = 740/870
50 mA RMS
600A/S2/P/S1196
C =620/740
100 mA RMS
600A/S3/P/S1222
C =620/740
100 mA RMS