P24xM
Operating time (Freq. Av Cycles setting = 0)
Reference conditions: To maintain accuracy, the minimum time delay setting should be:
Dt> 0.375 x Df + 0.23 (f0r Df setting <1 Hz)
Dt> 0.156 x Df + 0.47 (for Df setting >= 1 Hz)
5.6
LOAD RESTORATION
Pick-up
Drop-off
Restoration timer
Holding timer
5.7
ANTI-BACKSPIN
Pick-up
DT operation
Repeatability
P24xM-TM-EN-2.1
Operating time
<125 ms
Setting +/- 2.5%
0.95% x Setting +/- 2.5%
+/- 2% or 50 ms, whichever is greater
+/- 2% or 50 ms, whichever is greater
Setting ±5%
±2% or 50 ms whichever is greater
<1%
Chapter 21 - Technical Specifications
443