Chapter 6 - Current Protection Functions
P24xM
A typical setting for the negative sequence overcurrent element is 30% of the anticipated negative sequence
current resulting from loss of one phase during starting for a motor with a starting current to load current ratio of
6 to 1.
Therefore set:
I2>2 Current Set = 1/6 normal starting current or full load current
The setting for the alarm time delay is application dependent.