4.3
OPTO-INPUT TIME STAMPING
Each opto-input sample is time stamped within a tolerance of +/- 1 ms with respect to the Real Time Clock. These
time stamps are used for the opto event logs and for the disturbance recording. The device needs to be
synchronised accurately to an external clock source such as an IRIG-B signal or a master clock signal provided in
the relevant data protocol.
For both the filtered and unfiltered opto-inputs, the time stamp of an opto-input change event is the sampling time
at which the change of state occurred. If multiple opto-inputs change state at the same sampling interval, these
state changes are reported as a single event.