Figure 54: Zero Sequence Network Showing Residual Currents - GE P24DM Technical Manual

Motor protection ied
Table of Contents

Advertisement

P24xM
The unbalance current detected by a core balance current transformer on the healthy feeders can be seen to be a
simple vector addition of Ia1 and Ib1, giving a residual current which lies at exactly 90° lagging the residual
voltage. As the healthy phase voltages have risen by a factor of Ö3, the charging currents on these phases are also
·3 times larger than their steady state values. Therefore, the magnitude of residual current, IR1, is equal to 3 x the
steady state per phase charging current.
Note:
The actual residual voltage used as a reference signal for directional earth fault relays is phase shifted by 180° and is
therefore shown as -3 Vo in the vector diagrams. This phase shift is automatically introduced within the P24xM relays.
On the faulted feeder, the residual current is the addition of the charging current on the healthy phases (Ih3) plus
the fault current (If). The net unbalance is therefore equal to Il-Ih1-Ih2.
This situation is more readily observed by considering the zero sequence network for this fault condition. This is
shown in figure below.
I
L
3X
-V
L
0
V00640

Figure 54: Zero sequence network showing residual currents

When comparing the residual currents occurring on the healthy and the faulted feeders the figure below shows
that the currents would be similar in both magnitude and phase. Therefore, it is not possible to apply a relay which
could provide discrimination.
However, the scenario of no resistance being present in the coil or feeder cables is purely theoretical. Further
consideration needs to be given to a practical application in which the resistive component is no longer ignored.
P24xM-TM-EN-2.1
I
I
OF
ROF
I
ROH
I
ROH
IH
IH
IH
3
2
1
X
CO
Chapter 6 - Current Protection Functions
Faulty feeder
I
= Residual current on faulted feeder
ROF
I
= Residual current on healthy feeder
ROH
Healthy feeders
I
= I
– I
OF
L
H1
I
= I
+ I
ROF
H3
so:
I
= I
– I
ROF
L
H1
– I
– I
H2
H3
OF
– I
H2
127