APPENDIX D
D.1 CURRENT TRANSFORMERS
APPENDIX D APPENDIX DD.1 CURRENT TRANSFORMERS
D.1.1 GROUND FAULT CTS FOR 50:0.025 A
CTs that are specially designed to match the ground fault input of GE Power Management motor protection
relays should be used to ensure correct performance. These CTs have a 50:0.025A (2000:1 ratio) and can
sense low leakage currents over the relay setting range with minimum error. Three sizes are available with
3½", 5½", or 8" diameter windows.
D
GE Power Management
469 Motor Management Relay
D-1