Peterson Coil Earthed Systems; Figure 41: Current Level (Amps) At Which Transient Faults Are Self-Extinguishing - GE P24DM Technical Manual

Motor protection ied
Table of Contents

Advertisement

P24xM
We recommend the following RCA settings:
Resistance earthed systems: 0°
Distribution systems (solidly earthed): -45°
Transmission systems (solidly earthed): -60°
7.5.2

PETERSON COIL EARTHED SYSTEMS

A Petersen Coil earthing system is used in compensated earthing systems, as well as being used in cases of high
impedance earthing. Petersen Coil earthed systems (also called compensated or resonant systems) are commonly
found in areas where the system consists mainly of rural overhead lines. They are particularly beneficial in
locations which are subject to a high incidence of transient faults. In a Petersen Coil earthed system, the network is
earthed via a reactor, whose reactance is tuned to be nominally equal to the total system capacitance to earth.
Similar to insulated systems, if a single-phase to earth fault is applied to a Petersen Coil earthed system, under
steady state conditions no earth fault current flows. The effectiveness of the method in reducing the current to
zero is dependent on the accuracy of the tuning of the reactance value and any changes in system capacitance
(for example due to system configuration changes) require changes to the coil reactance. In practice, perfect
matching of the coil reactance to the system capacitance is difficult to achieve, so that a small earth fault current
will flow.
In isolated and compensated earthed systems, if an earth fault current is below a certain level, then the fault will
self-extinguish due to the low current magnitude. It therefore appears as a transient phenomenon. The figure
below shows earth fault current levels, below which they self-extinguish on these types of system. Statistics
demonstrate that around 80% of earth faults in Petersen Coil earthed systems self-extinguish. This, in part,
explains their popularity.
V00756

Figure 41: Current level (amps) at which transient faults are self-extinguishing

The following figure depicts a simple network earthed through a Petersen Coil reactance. It can be shown that if
the reactor is correctly tuned, theoretically no earth fault current will flow.
P24xM-TM-EN-2.1
Earth fault extinction current limits
as per DIN VDE 0228 Part 2
140
120
100
80
60
40
20
0
11kV
22kV
Residual fault current—compensated neutral
Capacitive fault current—isolated neutral
Chapter 6 - Current Protection Functions
33kV
65kV
110kV
115

Advertisement

Table of Contents
loading

This manual is also suitable for:

Micom p40 agileP24nm

Table of Contents