Resistance-Earthed Star Windings; Solidly-Earthed Star Windings; Figure 72: Ref Protection For Resistance-Earthed Systems; Figure 73: Ref Protection For Solidly Earthed System - GE P642 Technical Manual

Micom p40 agile transformer protection ied
Table of Contents

Advertisement

P64x
2.1

RESISTANCE-EARTHED STAR WINDINGS

Most distribution systems use resistance-earthed systems to limit the fault current. Consider the diagram below,
which depicts an earth fault on the star winding of a resistance-earthed Dyn transformer (Dyn = Delta-Star with
star-point neutral connection).
Source
V00669

Figure 72: REF Protection for resistance-earthed systems

The value of fault current (I
The value of earthing resistance (which makes the fault path impedance negligible)
The fault point voltage (which is governed by the fault location).
Because the fault current (I
fault.
A restricted earth fault element is connected to measure I
protection. The overall differential protection is less sensitive, since it only measures the HV current I
I
is limited by the number of faulty secondary turns in relation to the HV turns.
S
2.2

SOLIDLY-EARTHED STAR WINDINGS

Most transmission systems use solidly-earthed systems. Consider the diagram below, which depicts an earth fault
on the star winding of a solidly-earthed Dyn transformer.
Source
V00670

Figure 73: REF Protection for solidly earthed system

In this case, the fault current I
The leakage reactance of the winding
The impedance in the fault path
The fault point voltage (which is governed by the fault location)
In this case, the value of fault current (I
A restricted earth fault element is connected to measure I
protection.
P64x-TM-EN-1.3
87
I
F
I
S
I
F
) depends on two factors:
F
) is governed by the resistance, its value is directly proportional to the location of the
F
87
I
F
I
S
I
F
is dependent on:
F
) varies with the fault location in a complex manner.
F
Chapter 8 - Restricted Earth Fault Protection
1.0
Current p.u.
(x full load)
Pickup
0.2
64
Winding not protected
Fault position from neutral
directly. This provides very sensitive earth fault
F
10
8
Current p.u.
6
(x full load)
4
2
64
Fault position from neutral
directly. This provides very sensitive earth fault
F
I
F
I
S
20%
100%
(Impedance earthing)
S
I
F
I
S
20% 40%
60%
80%
100%
(Solid earthing)
. The value of
169

Advertisement

Table of Contents
loading

This manual is also suitable for:

P643P645

Table of Contents