Ariston NIMBUS HYBRID MODULE UNIVERSAL NET Manual page 84

Hide thumbs Also See for NIMBUS HYBRID MODULE UNIVERSAL NET:
Table of Contents

Advertisement

Available languages

Available languages

DESCRIPTION
5
5
7
Min T
5
5
8
Target deltaT for pump modulation cooling
12
HYBRID EVO 2 Param
12
0
User Parameters
12
0
0
Hybrid Mode
12
0
1
Energy Manager Logic
12
0
2
ECO / COMFORT
12
0
3
AUTO function
12
0
4
Quiet Mode Activation
12
0
5
Quiet Mode start time [hh:mm]
12
0
6
Quiet Mode end time [hh:mm]
12
0
7
Photovoltaic Integration
12
0
8
PV Delta T DHW setpoint temp.
12
1
Input Output Confi guration
12
1
0
HV Input 1
12
1
1
HV Input 2
12
1
2
HV Input 3
12
1
3
AUX Input 1
12
1
4
Uscita AUX 1 (AFR)
12
1
5
Uscita AUX 2
12
1
6
AUX P2 circulator setting
12
2
Energy manager parameter 1
12
2
0
Hydraulic scheme
12
2
1
FlowT HP Off set
12
2
2
Text for Boiler disabling
84 /
RANGE
7°C-MaxT [FC]; 18-MaxT [UFH]
[-5; -20°C]
Auto
Only Boiler
Only HP
Max Saving
Max Ecology
ECO PLUS
ECO
MEDIO
COMFORT
COMFORT PLUS
Absent
Present
OFF - ON
00:00 - 24:00
00:00 - 24:00
Not active
Active
0°C - 20°C
Not Defi ned
Absent
EDF
SG1
External switch off signal
Not Defi ned
Absent
DLSG
SG2
Not active
PV Integration Active
None
Humidistat sensor
None
Fault alarm
Humidistat alarm
External heat request
Cooling request
DHW request
None
Fault alarm
Humidistat alarm
External heat request
Cooling request
DHW request
Auxiliary circulator
Cooling circulator
Buff er circulator
None
WHB Combi
WHB + Tank
2°C - 10°C
Text for HP disabling - 0°C - 40°C
FACTORY SETTINGS
7°C [FC];
UFH
18°C [
]
-5°C
Auto
Max Ecology
MEDIO
Present
OFF
22:00
06:00
Not active
0°C
EDF
Absent
Not active
None
None
None
Auxiliary circulator
None
2°C
35°C

Advertisement

Chapters

Table of Contents
loading

Table of Contents