Ariston NIMBUS HYBRID MODULE UNIVERSAL NET Manual page 76

Hide thumbs Also See for NIMBUS HYBRID MODULE UNIVERSAL NET:
Table of Contents

Advertisement

Available languages

Available languages

Activate the heat pump in heating mode at fi xed frequency set by the
parameter 12.7.3
12.7.2
Rating Cooling Mode
Activate the heat pump in cooling mode at fi xed frequency set by the
parameter 12.7.3.
12.7.3
Compressor frequency setting
Defi ne the compressor frequency during the working mode of the heat
pump selected by the parameters 12.7.1 or 12.7.2.
In manual mode the heat pump keeps the protection logics active,
therefore the compressor frequency might be diff erent from the set one.
12.7.4
Fan 1 rpm setting
Defi ne the fan 1 velocity in RPM
12.7.7
Fan 2 rpm setting
Defi ne the fan 2 velocity in RPM
Press the OK button. Turn the knob and select:
12.8
TEST & UTILITIES
Press the OK button. Turn the knob and select:
12.8.0
Deaeration cycle
Activates the system deaeration cycle. The cycle lasts for 10 minutes.
Press the OK button. Turn the knob and select:
12.8.1
Screed drying cycle
Defi nes the screed drying programme for under-fl oor systems using the
following values:
- 0. OFF
- 1. Functional (screed heating at a fi xed temperature of 55°C for a 6
day period)
60
55
50
45
40
35
30
25
20
15
0
1
2
3
Period (days)
- 2. Ready to use (screed heating at a variable temperature from 25°C
to 55°C for the duration shown in the graph for an 18 day period)
60
55
50
45
40
35
30
25
20
15
0
2
4
6
Period (days)
- 3. Functional + Ready to use (screed heating at a fi xed temperature of
55°C for a 6 day period, at a variable temperature from 25°C to 55°C
for the duration shown in the graph in the following 18 days)
76 /
4
5
6
7
8
9
8
10
12
14
16
18
60
55
50
45
40
35
30
25
20
15
0
- 4. Ready to use + Functional (screed heating at a variable tempera-
ture from 25°C to 55°C for the duration shown in the graph, for an 18
day period, at a fi xed temperature of 55°C in the following 6 days)
60
55
50
45
40
35
30
25
20
15
0
- 5. Manual (screed heating at temperature set in parameter 12.3.9)
Press the OK button. Turn the knob and select:
12.8.5
Refrigerant Recover
Activate this function to recover the refrigerant gas before every mainte-
nance operation on the refrigerant circuit.
10
Turn the knob and select:
12.9
ENERGY TARIFF SETTING
Press the OK button. Turn the knob and select:
12.9.0
Min Admit Electricity/Gas Cost Ratio
Defi nes the minimum allowed ratio (0.5) between the electrical kWh and
gas unit costs.
Press the OK button. Turn the knob and select:
12.9.1
Max Admit Electricity/Gas Cost Ratio
Defi nes the maximum allowed ratio (4) between the electrical kWh and
gas units costs.
Press the OK button. Turn the knob and select:
12.9.2
Primary/Elec Energy Ratio (Valx100)
Defi nes the conversion factor between primary energy and electrical
energy consumed by the heat pump.
Press the OK button. Turn the knob and select:
12.9.3
Gas kWh cost (GCV)
Defi nes the gas cost per kWh consumed
20
12.9.4
Electricity kWh cost
5
10
15
20
Period (days)
5
10
15
20
Period (days)
25
30
25
30