CHAPTER 5: CONFIGURING THE BUILT-IN NOTIFICATIONS
The logic will ignore all other intermediate physical sensor statuses and only changes the virtual sensor's state back if it
exactly matches the specified physical sensor status (RESET Source Sensor).
Choose your unit, physical sensor, and the status you'd like the logic to monitor.
NOTE: If you connect an expansion board, you'll be able to select sensors from the expansion board also.
On this example picture, we've set the logic to change the virtual sensor to Critical if the Temperature sensor's status
becomes High Critical, and only change it back to Normal when the Temperature sensor's status also becomes Normal.
FIGURE 5-85. FLIPFLOP LOGIC SCREEN
FIGURE 5-86. FLIPFLOP LOGIC EXAMPLE