Earthing the safety light grid

Please note:
Connect the 0 V connections on all the 24 V power supplies and earth the 0 V mains at
}
a single point, or ensure that measures are in place to monitor for earth faults.
The connection of the 0 V supply to the central earth bar or earth fault monitor must be
}
in accordance with relevant national regulations (such as EN 60204-1, NFPA 79:17-7,
NEC: Article 250).
Connections should be protected from corrosion.
}
Flexible earthing straps should be used on moving earth parts (e.g. machine parts,
}
gates). Ensure these earthing straps are as short and wide as possible.
Operating Manual PSEN op2H-SL Series
1004304-EN-01