PSEN op2H-SL Series
Fig.: Timing diagram for EDM
Legend
t
1
t
2
Use control elements whose dynamics match the times stated at t
The function is activated or deactivated with the

Cascading

During cascading, the safety outputs of a safety light grid are connected to an evaluation
device. A second safety light grid can be connected to this first safety light grid. The first
safety light grid is the master unit; the safety light grid connected to the master unit is the
slave unit.
Max. 2 slave units to one master unit
}
Max. overall length: 3600 mm
}
The master unit collects the results from the slave units and ensures synchronisation
}
between them, so that mutual interference is avoided
Each transmitter/receiver in the PSEN op2H-SL Series can be used both as a master
}
unit and a slave unit
Up to three areas can be monitored when two safety outputs are connected
}

Project configuration

Maintaining the safety distance

The minimum distance between the safety light grid and the hazardous machine compon-
ent should be such that the operator cannot reach the hazardous area until the hazardous
machine part has come to a standstill.
Operating Manual PSEN op2H-SL Series
1004304-EN-01
On
OSSD
Off
24 V
EDM
0 V
After the OSSD outputs are switched on, the EDM circuit must open within 350 ms
After the OSSD outputs are switched off, the EDM circuit must close within 100 ms
t
t
1
2
1
Wiring [
30].
and t
.
2
13