7. Tighten the screws on the brackets with the max.
Check that the green LED on the receiver is lit.
}
Check that the safety light grid operates correctly.
}
If a single light beam is interrupted by an opaque object
For this test you should use a test rod for a safety light grid with a resolution of 24 mm.
}

LED indicators in alignment mode

1
yel-
low
yel-
low
yel-
low
yel-
low

Commissioning

System connection

Make sure that the selected evaluation device has the following properties:
2-channel with feasibility monitoring
}
OSSD signals are evaluated
}
Suitable Pilz evaluation devices are, for example:
PNOZelog for monitoring safety light grids
}
PNOZsigma for monitoring safety light grids
}
PNOZ X for monitoring safety light grids
}
Operating Manual PSEN op2H-SL Series
1004304-EN-01
the green LED must go out,
the red LED must light and
the safety light grid must switch to a safe state.
2
EDM/3
RES
yel-
low
yel-
yel-
low
low
yel-
yel-
yel-
low
low
low
torque [
Meaning
OSSD
PWR
Safety light grid not aligned, no synchron-
isation of first and last light beams.
red
green
Synchronisation of first and last light beams.
One or more light beams are interrupted.
red
green
Synchronisation of first and last light beams.
Weak signal strength.
green green
Protected field is clear.
Synchronisation of first and last light beams.
Medium signal strength.
green green
Protected field is clear.
Synchronisation of first and last light beams.
Medium signal strength.
green green
Protected field is clear.
43].