9.2

System error messages

Code
Description
A102
checksum error
general reset & new calibr.
required
W103
initialising - please wait
A106
downloading please wait
A110
checksum error
general reset & new calibr.
required.
A111
electronics defect
A113
electronics defect
A114
electronics defect
A115
electronics defect
A116
download error
repeat download
A121
electronics defect
W153
initialising - please wait
A160
checksum error
general reset & new calibr.
required.
A164
electronics defect
A171
electronics defect
A221
Probe pulse deviation from
average values
A241
Broken probe
A251
Feedthrough
A261
HF cable defective
W275
Offset too high
W512
recording of mapping please
wait
Possible cause
device has been powered off before data
could be stored;
emc problem;
2
E
PROM defect
2
E
PROM storage not yet finished
processing data download
device has been powered off before data
could be stored;
emc problem;
2
E
PROM defect
RAM defective
ROM defective
2
E
PROM defective
general hardware problem
checksum of stored data not correct
2
no factory calibration existant; E
PROM
defective
initialisation of electronics
device has been powered off before data
could be stored;
emc problem;
2
E
PROM defect
hardware problem
hardware problem
HF module or cable between HF module
and electronics defective
Broken probe orvalue for probe length is
too short
Lost contact in the process feedthrough
HF cable defective or HF connector
removed
Temperature at the electronics too high or
HF module defective
mapping active
Trouble-shooting
Remedy
reset
avoid emc problem;
if alarm prevails after reset,
exchange electronics
wait some seconds; if warning
prevails, exchange electronics
wait until warning disappears
reset
avoid emc problem;
if alarm prevails after reset,
exchange electronics
reset
if alarm prevails after reset,
exchange electronics
reset
if alarm prevails after reset,
exchange electronics
reset
if alarm prevails after reset,
exchange electronics
Reset
if alarm prevails after reset,
exchange electronics
restart download of data
contact service
wait some seconds; if warning
prevails, power off device and
power on again
reset
avoid emc problem;
if alarm prevails after reset,
exchange electronics
reset
if alarm prevails after reset,
exchange electronics
reset
if alarm prevails after reset,
exchange electronics
Check contacts on HF module
If fault cannot be eliminated:
Replace HF module
Check the probe length in 033,
Check the probe itself,if the probe is
broken, change the probe, or
change to a non contact system
Replace process feedtrough
Check HF connector, replace cable
if defective
Check temperature, replace HF
module if defective
wait some seconds until alarm
disappears
69