Levelflex M FMP45 with HART/4...20 mA
⇒
ENDRESS + HAUSER
–
+
E
⇒
ENDRESS + HAUSER
–
+
E
Endress + Hauser
After selection "length too short" or "length too long", the calculation of the new value need approx.
10 s.
Function "empty calibr." (005)
This function is used to enter the distance from the flange (reference point of the measurement) to
the minimum level (=zero).
E
Function "full calibr." (006)
This function is used to enter the distance from the minimum level to the maximum level (=span).
E = empty calibration (= zero)
E max = probe length – lower blocking distance
0%
Commissioning
L00-FMP4xxxx-14-00-06-en-008
49