Brief Operating Instructions Levelflex M FMP45 Interface Guided Level-Radar These are Brief Operating Instructions. For more detailed information, please refer to the Operating Instructions and the additional documentation on the CD-ROM provided. These Brief Operating Instructions are not intended to replace the Operating Instructions provided in the scope of supply.
Levelflex M FMP45 4 to 20 mA HART Safety instructions Safety instructions Designated use The Levelflex M is a compact level transmitter for the continuouse measurement of solids and liquids, measuring prinziple: Guided Level Radar / TDR: Time Domain Reflectometry.
Safety instructions Levelflex M FMP45 4 to 20 mA HART Safety icons Symbol Meaning Warning! A warning highlights actions or procedures which, if not performed correctly, will lead to personal injury, a safety hazard or destruction of the device. "...
Levelflex M FMP45 4 to 20 mA HART Mounting Mounting Quick installation guide Mounting with threaded boss F12/F23 or T12 housing 1½" AF 60 Caution! Use only the threaded boss L00-FMP4xxxx-17-00-00-en-072 Incoming acceptance, transport, storage 2.2.1 Incoming acceptance Check the packing and contents for any signs of damage. Check the shipment, make sure nothing is missing and that the scope of supply matches your order.
Mounting Levelflex M FMP45 4 to 20 mA HART Installation 2.3.1 Mounting kit In addition to the tool needed for flange mounting, you will require the following tool: • For the mounting of threaded connection: 60 mm Open-end spanner for 1½".
Page 7
Levelflex M FMP45 4 to 20 mA HART Mounting Separable probes If there is little mounting space (distance to the ceiling), it is advisable to use separable rod probes (∅16 mm). • max. probe length 10 m (394 in) • max. sideways capacity 20 Nm •...
Page 8
Mounting Levelflex M FMP45 4 to 20 mA HART 2.3.4 Special information on interface measurement Installation in horizontal cylindrical, upright and underground tanks • Use coax probes or rod probes in the bypass/stilling well. A segmented probe is available as a special version for longer measuring ranges.
Page 9
Levelflex M FMP45 4 to 20 mA HART Mounting Installation in stilling well or bypass • A rod probe can be used for pipe diameters bigger than 40 mm. • Rod probe installation can take place up to a diameter size of 100 mm. In the event of larger diameters, a coax probe is recommended.
Mounting Levelflex M FMP45 4 to 20 mA HART 2.3.5 Turn housing After mounting, the housing can be turned 350° in order to simplify access to the display and the terminal compartment. Proceed as follows to turn the housing to the required position: •...
Levelflex M FMP45 4 to 20 mA HART Wiring Wiring Warning! When using the measuring device in hazardous areas, installation must comply with the corresponding national standards and regulations and the Safety Instructions or Installation or Control Drawings. " Caution! Before connection please note the following: •...
Wiring Levelflex M FMP45 4 to 20 mA HART Wiring in T12 housing Unscrew housing cover (1). Insert cable (2) through gland (3). Connect cable screen to the grounding terminal (4) within the terminal compartment. Make connection (see terminal assignment).
Levelflex M FMP45 4 to 20 mA HART Wiring Connecting the measuring unit Load HART Minimum load for Hart communication: 250 Ω Ground connection It is necessary to make a good ground connection to the ground terminal on the outside of the housing, in order to achieve EMC security.
Wiring Levelflex M FMP45 4 to 20 mA HART Overvoltage protection If the measuring device is used for the level measurement in flammable liquids which requires the use of an overvoltage protection according to EN/IEC 60079-14 or EN/IEC 60060-1 (10 kA, Puls 8/20 μs) it has to be ensured that •...
Levelflex M FMP45 4 to 20 mA HART Operation Operation General structure of the operating menu The operating menu is made up of two levels: • Function groups (00, 01, 03, …, 0C, 0D): The individual operating options of the device are split up roughly into different function groups.
Operation Levelflex M FMP45 4 to 20 mA HART The third digit numbers the individual functions within the function group: → • basic setup • tank properties • medium properties • process cond. Here after the position is always given in brackets (e.g. "tank properties" (002)) after the described function.
Page 17
Levelflex M FMP45 4 to 20 mA HART Operation 4.2.2 Display Primary measuring value Position indicator ENDRESS + HAUSER Description Secondary measuring value Unit Symbol – Selection list Function groups -> Functions HOME F000 F001 F002 F003 F004 ... FG00...
Page 18
Operation Levelflex M FMP45 4 to 20 mA HART 4.2.3 Display symbols The following table describes the symbols that appear on the liquid crystal display: Symbol Meaning ALARM_SYMBOL This alarm symbol appears when the device is in an alarm state. If the symbol flashes, this indicates a warning.
Levelflex M FMP45 4 to 20 mA HART Commissioning Commissioning Function check Make sure that all final checks have been completed before you start up your measuring point: • Checklist "Post-installation check", → ä 10. • Checklist "Post-connection check", → ä 14.
Commissioning Levelflex M FMP45 4 to 20 mA HART Overview Basic Setup flange: reference point of measurement = empty calibr. (= zero) - setting in 005 = full calibr. (= span) - setting in 006 = distance interface (distance flange / DK ) - display in 0A6...
Page 21
Levelflex M FMP45 4 to 20 mA HART Commissioning " Caution! The basic setup is sufficient for successful commissioning in most applications. The Levelflex is precalibrated at the factory to the probe length ordered so that in most cases only the application parameters that automatically adapt the device to the measuring conditions need to be entered.
Commissioning Levelflex M FMP45 4 to 20 mA HART Basic Setup with the device display 5.4.1 Function "measured value" (000) ⇒ ENDRESS + HAUSER – This function displays the current measured value in the selected unit (see"Customer unit" (042) function). The number of digits after the decimal point can be selected in the "No.of Decimals"...
Page 23
Levelflex M FMP45 4 to 20 mA HART Commissioning Partially Filled The system searches for 2 signals in the measuring range. The upper signal is assigned to the total level and the lower signal to the level of the interface layer. The difference between the two levels corresponds to the thickness of the upper medium (upper phase).
Page 24
Commissioning Levelflex M FMP45 4 to 20 mA HART 5.4.5 Function "empty calibr." (005) ⇒ ENDRESS + HAUSER – This function is used to enter the distance from the flange (reference point of the measurement) to the minimum level (= zero).
Page 25
Levelflex M FMP45 4 to 20 mA HART Commissioning 5.4.6 Function "full calibr." (006) ⇒ ENDRESS + HAUSER – This function is used to enter the distance from the minimum level to the maximum level (= span). 100% F = full calibration (= span) F max = E –...
Page 26
Commissioning Levelflex M FMP45 4 to 20 mA HART 5.4.7 Function "Upper Block. Dist" (059) ⇒ ENDRESS + HAUSER – For rod and rope probes with lengths of up to 8 m, the upper blocking distance is preset to 0.2 m on delivery.
Page 27
Levelflex M FMP45 4 to 20 mA HART Commissioning 5.4.8 Maximum measured error Typical data under reference operating conditions: DIN EN 61298-2, percentage values in relation to the span. Output: digital analog Sum of non-linearity, Level (level and interface electronics versions): ±0.06 %...
Page 28
Commissioning Levelflex M FMP45 4 to 20 mA HART If the DC value is less than 7 for rope probes, then measurement is not possible in the area of the tensioning weight (0 to 250 mm from end of probe; lower blocking distance).
Page 29
Levelflex M FMP45 4 to 20 mA HART Commissioning ε ε DC ( Typical liquids DC ( Typical liquids – Benzene, styrene, toluene 1.4 to 1.6 – Liquefied gases, e. g. N , CO 2.5 to 4 – Furan – Naphthalene –...
Commissioning Levelflex M FMP45 4 to 20 mA HART Envelope curve with device display After the basic setup, an evaluation of the measurement with the aid of the envelope curve "envelope curve" (0E) function group) is recommended. 5.5.1 Function "plot settings" (0E1) Here you can select which information is shown on the display: •...
Page 31
Levelflex M FMP45 4 to 20 mA HART Commissioning Endress+Hauser...