Commissioning
!
54
Maximum measured error
Typical statements for reference conditions:
DIN EN 61298-2, percentage of the span.
Output:
digital
sum of non-linearity,
measurig range:
non-repeatability
– up to 10 m: ±3 mm
and hysteresis
– > 10 m: ± 0.03 %
for PA coated rope
measuring range:
– up to 5 m: ±5 mm
– > 5 m: ± 0.1 %
Offset / Zero
±4 mm
If the reference conditions are not met, the offset/zero arising from the mounting situation may be
up to ±12 mm. This additional offset/zero can be compensated for by entering a correction
(function "offset" (057)) during commissioning.
Differing from this , the following measuring error is present in the vicinity of the probe end:
rod probe and coax probe
80
60
40
20
0
-20
-40
-60
-80
0
50
100
150
distance from probe end [mm]
Note!
Please reenter the blocking distance in the function group "extended calibr." (05) function
"upper block.dist" (059) when installing the device in a high nozzle: upper blocking distance (UB)
= nozzle height (H) + 50 mm.
Levelflex M FMP45 with HART/4...20 mA
analogue
± 0.06 %
± 0.03 %
DC = 2
DC > 7
-20
-40
-60
-80
200
250
300
L00-FMP4xxxx-05-00-00-en-001
rope probe
80
60
DC > 7
40
20
0
0
50
100
150
200
distance from probe end [mm]
L00-FMP4xxxx-05-00-00-en-002
H
UB
50
L00-FMP4xxxx-14-00-06-xx-001
Endress + Hauser
250
300