7. Voltage measurement

# DANGER
●   D o not apply a voltage exceeding the measuring range, 600 V max., to the 
instrument.
● Keep your fingers behind the barrier during a measurement.
●   V erify  proper  operation  on  a  known  source  before  taking  actions  as  a 
result of the indication of the instrument.

7-1 Measurement method

(1)   S et the function switch to V/ Ω position. To measure low-resistance, press   
the SELECT button (< 1 sec.).
(2) Connect the test leads as the following figure shows. 
   - MODEL7260 to the LINE terminal
   - MODEL7261A to the EARTH terminal
Red
(3)   C onnect the black test lead to the earth side of the circuit under test and 
the red remote probe to the line side. 
CAUTION
Never press the
test button.
̶  18  ̶
www.calcert.com
15
10
20
5
25
0
30
Fig. 7-1
Black
CAUTION
Never press the
remote-control switch.
Select V/ Ω Range.
Fig. 7-2