KYORITSU KEW3552 Instruction Manual

KYORITSU KEW3552 Instruction Manual

Insulation - continuity tester
Hide thumbs Also See for KEW3552:
Table of Contents

Advertisement

Quick Links

1.888.610.7664
Instruction manual
INSULATION - CONTINUITY TESTER
KEW3551/3552/3552BT
www.calcert.com
15
10
20
5
25
0
30
sales@calcert.com

Advertisement

Table of Contents
loading

Summary of Contents for KYORITSU KEW3552

  • Page 1 Instruction manual INSULATION - CONTINUITY TESTER KEW3551/3552/3552BT 1.888.610.7664 www.calcert.com sales@calcert.com...
  • Page 2: Table Of Contents

        8-1 Measurement method ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 21     8-2 Continuous measurement ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 23     8-3 Voltage characteristics of measurement terminals ・・・・・・・・・・・・・・・・ 24     8-4 20G/ 40GΩ range (3552/3552BT only) ・・・・・・・・・・・・・・・・・・・・・・・ 25         8-4-1 Settings  ・ ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 25     8-5 Insulation status indicator ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 26         8-5-1 Reference value for insulation status, Pass/ Fail, judgement  ・ ・・・・・・・・・・ 26         8-5-2 Reference value settings ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 27     8-6 DAR/ PI measurement, 1-min value display (KEW3552/3552BT only) ・・・・・・・・・ 29         8-6-1 DAR/ PI measurement and 1-min value display  ・ ・・・・・・・・・・・・・ 29         8-6-2 Indication ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 29 9. Low-resistance measurement (Continuity check) ・・・・・・・・・・・・・・・・・・・・・ 30     9-1 Zero Ω ADJ. function  ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 30     9-2 Measurement ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 30 10. LCD backlight, LED light, Buzzer ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 31     10-1 LCD backlight  ・ ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 31     10-2 Buzzer ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・...
  • Page 3 13. Memory function (KEW3552/ 3552BT only) ・・・・・・・・・・・・・・・・・・・・・・・ 37     13-1 Saving method ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 37     13-2 Recalling the data ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 38     13-3 Deleting the data  ・ ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 39 14. Infrared data transmission (KEW3552/ 3552BT only)  ・ ・・・・・・・・・・・・・・ 40     14-1 How to transfer data ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 40 15. Bluetooth communication (KEW3552BT only) ・・・・・・・・・・・・・・・・・・・・・・ 41     15-1 Bluetooth communication ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 41     15-2 KEW Smart for KEW3552BT ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 42 16. Battery replacement ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 43 17. Shoulder strap belt attachment  ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 44 18. Storing in carrying case ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 44 1.888.610.7664 www.calcert.com sales@calcert.com...
  • Page 4: Safety Warnings (Safety Precautions) ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・1

    ● The instrument is to be used only in its intended applications. ●   U nderstand and follow all the safety instructions contained in the manual. It  is essential that the above instructions are adhered to. Failure to follow the  above instructions may cause injury, instrument damage and/or damage to  equipment  under  test.  Kyoritsu  is  by  no  means  liable  for  any  damage  resulting from the instrument in contradiction to these cautionary notes.  The symbol # indicated on the instrument means that the user must refer to  the  related  parts  in  the  manual  for  safe  operation  of  the  instrument.  It  is  essential  to  read  the  instructions  wherever  the  symbol  #  appears  in  the ...
  • Page 5 ●   V erify proper operation on a known source before use or take actions as a  result of the indication of the instrument. # WARNING ●   D o not use the instrument or test leads if any abnormal conditions, such  as broken cover or exposed metal parts are noted.  ●   F irst, firmly connect the test leads to the instrument, and then press the  test button.  ● Never install substitute parts or make any modifications to the instrument.      S end the instrument to your local KYORITSU distributor for repair or re-  calibration. ● Do not try to replace batteries if the surface of the instrument is wet. ● Connect each test lead firmly into the corresponding terminals.  ●   S top  using  the  test  lead  if  the  outer  jacket  is  damaged  and  the  inner  metal or color jacket is exposed. ●   E nsure that the function switch is set to OFF position before opening the  battery compartment cover for battery replacement.
  • Page 6 Symbols The  following  symbols  are  used  and  marked  on  the  instrument  and  in  this  instruction  manual.  Please  carefully  check  before  starting  to  use  the  instrument.   Double or reinforced insulation User  must  refer  to  the  explanations  in  the  instruction  manual.   Earth Danger of possible electrical shock Do not use on AC electric systems exceeding 660 V.
  • Page 7: Features ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・4

    2. Features KEW3551/3552/3552BT can measure insulation resistance, low-resistance,  and also AC/ DC voltage. ●   L CD backlight and LED spot light to facilitate working at dimly illuminated  location or at nighttime work. The built-in illuminance sensor automatically  turns on/ off the lights.  ● Memory function (available on KEW3552/ 3552BT)   Internal memory to save, recall, and delete the measured data. ● Infrared transmission function (available on KEW3552/ 3552BT)   Transmits the data saved in the internal memory to PC. ● Bluetooth communication function (available on KEW3552BT)     C onnects  the  instrument  and  a  Bluetooth  device,  like  a  tablet,  for  remote  monitoring and data saving. ● Clock (available on KEW3552/ 3552BT)   Measured data is saved with the measurement time information. ● Auto-power off function    ...
  • Page 8   - With elapsed time display         S tarts counting and displaying testing duration, elapsed time, on the start  of insulation resistance measurement.   - DAR/ PI measurement function (available on KEW3552/ 3552BT)         A utomatically  calculates  and  displays  DAR  (Dielectric  Absorption  Ratio)  and  PI  (Polarization  Index)  values  during  an  insulation  resistance  measurement. ● Zero-ohm adjustment function     F or  low-resistance  measurements,  short-circuit  the  tips  of  test  leads  and ...
  • Page 9 Overview of available function list  Function KEW3551 KEW3552 KEW3552BT Voltage measurement 20G/40GΩ Range Insulation  Insulation status  Fixed Pass/  User selectable Pass/  Meas. indicator Fail criteria Fail criteria DAR/ PI Zero ADJ. Low- resistance  Meas. Continuity buzzer Backlight Memory Clock (MODEL8212USB) Data Communication Wireless (via Bluetooth) ̶  6  ̶ 1.888.610.7664 www.calcert.com sales@calcert.com...
  • Page 10: Specifications ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・7

    3. Specifications ● Measuring range and accuracy (at 23℃±5℃, RH 85% or less) 1. Voltage measurement Range 300.0/ 600 V (auto-ranging) AC  300.0 V : 0.0 to 314.9 V   600.0 V : 270 to 629 V Display range DC  300.0 V : ± 0.0 to ± 314.9 V    600 V : ± 270 to 849 V Measuring range AC: 2.0 to 600 V rms (45 ‒ 65 Hz) (accuracy guaranteed) DC: ± 2.0 to ± 600 V AC: > 629 V Over-range display DC (+) : > 849 V DC (-) : < - 849 V Accuracy ±1%rdg±4dgt  *   R MS  detection  in  AC  mode.  For  non-sinusoidal  waveforms  with  CF<2.5,  add ±1%rdg for the above listed accuracy. (850 Vpeak or less). AC/ DC  auto-detection (2 V or higher) 2. Low-resistance measurement (Continuity check) Resistance range 40.00/ 400.0/ 4000 Ω (auto-ranging) Open-circuit V...
  • Page 11 360 - 524 104.9 MΩ 209.9 MΩ 262.4 MΩ 20 GΩ: 40 GΩ: MΩ  1.80 - 20.99 GΩ 3.60 - 41.99 GΩ KEW3551 >2099 MΩ >4199 MΩ KEW3552/3552BT O v e r - r a n g e  >104.9 >209.9 >262.4 >524  While 20/ 40GΩ Range is enabled:  display MΩ MΩ MΩ MΩ (if  disabled,  the  display  is  the  same ...
  • Page 12 ● Applicable  ●   I EC 61010-1, -2-034 CAT IV 300 V/ CAT III 600 V    standards Pollution degree 2 ● IEC 61557-1, -2, -4, -10 ● IEC 61326-1, 2-2 ● IEC 60529 (IP40) ● EN 50581 (RoHS) ● IEC 61010-031     MODEL7260  CAT III 600 V (w/ cap)     CAT II 1000 V (w/o cap)     CAT II 1000 V (w/ 8017A)     ( Attach the supplied protective cap to use this test  leads in CAT III or higher environments.)   MODEL7261A  CAT III 600 V (w/ alligator clip)     CAT II 600 V (w/ flat test bar)     ( Attach  the  supplied  alligator  clip  to  use  this  test  leads in CAT III or higher environments.)   *  ...
  • Page 13 ● Operating uncertainty     O perating uncertainty (B) is an error obtained under the nominal operating  conditions and calculated with the intrinsic error (A), which is an error of  the instrument used, and the error (En) due to variations. According to the  standard, IEC 61557, the maximum operating error should be within ±30  %.  Intrinsic  error  (A)  is  uncertainty  of  the  performance  characteristics  of  the instrument in the reference condition.  1.   O perating uncertainty of insulation resistance measurement (IEC61557-2)   * Formula: B = ±(|A|+ 1.15 x  √E  + E  + E Intrinsic error Influence of position (N/A for digital testers) Influence of supply voltage (until battery status indicator becomes empty Influence of temperature (0℃ - 35℃) The specs. of this instrument are as follows. Intrinsic error (A)  ......within ±5 % of indicated value   (coverage factor: k=2) Influence of supply voltage (E )  ..within ±5 % of indicated value Influence of temperature (E ) ...
  • Page 14 ●   P ossible  number  of  measurements  where  battery  voltage  is  within  the  effective range. (measurement of 5 sec., pause of 25 sec.) Measurement function Test resistor Possible number of measurements 50 V 0.050 MΩ 2000 times or more 100 V 0.100 MΩ 1600 times or more 125 V 0.125 MΩ 1600 times or more Insulation Resistance 250 V 0.25 MΩ 1300 times or more 500 V 0.5 MΩ 1300 times or more 1000 V 1 MΩ 700 times or more Low-resistance  1 Ω 1400 times or more * where:    ...
  • Page 15: Instrument Layout

    Turns  on/  off  the  0Ω  ADJ  function  at  low-resistance  ( ) measurement. KEW3551: COMP button ⑨ *   F or KEW3551: also used to turn on/ off insulation status indicator. KEW3552/ 3552BT:  *   F or KEW3552/ 3552BT: also used to make settings of each function. SETUP button A long press (  1 sec.) while measuring 125 V switches a  measurement range to 100 V range; a short press (<1 sec.)  ⑩ SELECT button at  voltage  measurement  switches  the  function  to  low- resistance measurement. Switches  measurement  functions  and  selects  voltage  for ...
  • Page 16 2. Side panel ③ Fig. 4-2 ① ② Name Description ① LINE terminal To connect MODEL7260 test lead. ② EARTH terminal To connect MODEL7261A test lead. Illuminates  the  measurement  spot.  The  light  auto- ③ LED spot light matically  turns  on/  off  depending  on  the  ambient  brightness. 3. LCD Fig. 4-3 Name Description Battery status indicator Bar graph display of insulation resistance Digital display with measurement unit...
  • Page 17 > symbol  appears  when  the  measured  value  is  exceeding  the  measuring  range,  and < symbol  appears when the measured dc has negative polarity. Appears when 0ΩADJ is done. Appears at Bluetooth communication (3552BT only) Buzzer ON Appears at IR communication (3552/ 3552BT only) Blinks while adjusting time (3552/ 3552BT only) Indicates a DAR value is displayed. (3552/ 3552BT  only) Indicates  a  PI  value  is  displayed.  (3552/  3552BT  only) Indicates 1-min value is displayed.  Comparator function is enabled. Indicates  the  rated  measurement  voltage  value  selected at insulation resistance measurement.
  • Page 18: Accessories

    5. Accessories ● Test leads (1) Teat lead with remote control switch MODEL7260 (red) *1 Barrier Metal tip Attach the supplied detachable cap as necessary.   Insulation cap For CAT III 600 V (w/ cap) Fig. 5-1 For CAT II 1000 V (w/o cap) (2) Extension prod MODEL8017A    * Attached and used with MODEL7260.  Long type and helpful to access the distant measurement spot Fig.
  • Page 19: Getting Started

    6. Getting started 6-1 Attaching metal tip/ adapter for test leads The  following  metal  tips  and  adapters  are  user-changeable  depending  on  measurement purposes. (1) For MODEL7260   The following metal tips are available.   1. Standard metal tip  ..  I n stalle d  at  a  s hip m e nt  s u p plie d  wit h  a  detachable insulation cap.
  • Page 20: Battery Voltage Check

    # DANGER To avoid getting electrical shocks, disconnect the test leads from the  instrument before replacing the metal tip or adapter. 6-2 Battery voltage check (1)   P lease refer to 16. Battery replacement in this manual and insert batteries  in the instrument. (2)   S et  the  function  switch  to  any  position  other  than  OFF  to  power  on  the  instrument.  (3)   C heck the battery status indicator displayed at the upper left corner of the  LCD.      : Normal. Battery voltage is enough.     :   L ow  battery  voltage:For  continuous  measurement,  please  refer  to ...
  • Page 21: Voltage Measurement

    7. Voltage measurement # DANGER ●   D o not apply a voltage exceeding the measuring range, 600 V max., to the  instrument. ● Keep your fingers behind the barrier during a measurement. ●   V erify  proper  operation  on  a  known  source  before  taking  actions  as  a  result of the indication of the instrument. 7-1 Measurement method (1)   S et the function switch to V/ Ω position. To measure low-resistance, press    the SELECT button (< 1 sec.). (2) Connect the test leads as the following figure shows.     - MODEL7260 to the LINE terminal    - MODEL7261A to the EARTH terminal Fig. 7-1 Black (3)   C onnect the black test lead to the earth side of the circuit under test and  the red remote probe to the line side. ...
  • Page 22 (4)   C heck the reading on the LCD without pressing the test button nor remote  control  switch.  The  instrument  detects  ac/  dc  automatically,  and  shows  DC for dc input and AC for ac input.  ●   W hen  negative  dc  voltage  is  defected  at  the  line  probe  side,  minus  - polarity sign is displayed with a measured value. ●   I f  the  measured  voltage  is  less  than  2  V,  AC/  DC  auto-detection  doesn t  work.
  • Page 23: 8 Insulation Resistance Measurement

    8 Insulation resistance measurement This instrument is used to measure insulation resistance of electric appliance  or  circuit  to  inspect  the  insulation  performance.  Check  the  voltage  rating  of  the  object  to  be  tested  before  making  measurement  and  select  the  voltage  applied to.  Note: ●   D epending  on  the  object  to  be  measured,  displayed  insulation  resistance  value may not stabilize. ...
  • Page 24: Measurement Method

    8-1 Measurement method (1) Connect the test leads as the following figure shows.     - MODEL7260 to the LINE terminal    - MODEL7261A to the EARTH terminal Fig. 8-1 Black (2)   C onfirm  that  the  circuit  under  test  isn t  energized,  and  measure  voltage  with reference to 7. Voltage measurement. (3)   C onfirm  the  voltage  value  which  can  be  applied  to  the  circuit  under  test,  and then set the function switch to the desired range.
  • Page 25   Source side Earth terminal Circuit breaker Black Load side Fig. 8-2 Indicates the elapsed time. Fig. 8-3 (6) Auto discharge function This  function  allows  electric  charges  stored  in  the  capacitance  of  the  circuit  under  test  to  be  automatically  discharged  after  measurement.  Set  the  test  button or remote-control switch to off with the test leads connected. ...
  • Page 26: Continuous Measurement

    ● Bar graph     D epending on the selected measurement range, values on each tick of bar  graph vary as shown below. Bar graph for 500 V/ 1000 V range Fig. 8-4 Bar graph for 50 V/ 100 V/ 125 V/ 250 V range Fig. 8-5 8-2 Continuous measurement For  continuous  measurement,  use  the  lock-down  feature  incorporated  on  the  test ...
  • Page 27: Voltage Characteristics Of Measurement Terminals

    8-3 Voltage characteristics of measurement terminals This  instrument  conforms  to  IEC61557.  This  standard  defines  that  the  rated  measurement  current  shall  be  at  least  1  mA,  and  the  lower  limit  of  the  insulation  resistance  maintaining  the  rated  measurement  voltage  at  measurement  terminals.  (See  the  table  below.)  This  value  is  calculated  by  dividing the rated voltage by rated current. ie., in case that the rated voltage is ...
  • Page 28: 40Gω Range (3552/3552Bt Only)

    8-4 20G/ 40GΩ range (3552/3552BT only) The 20GΩ and 40GΩ ranges are available for measuring 500 V and 1000 V  respectively. (This is NOT available on KEW3551.)  Enabling/  disabling  2 0 GΩ/  4 0 GΩ  range  affects  and  changes  the  configurations of 500V and 1000V ranges as shown in the following table. 1. While 20GΩ/40GΩ ranges are disabled (default settings): Voltage Four measurement ranges 500V 4.000 MΩ/ 40.00 MΩ/ 400.0 MΩ/ 2000 MΩ 1000V 4.000 MΩ/ 40.00 MΩ/ 400.0 MΩ/ 4000 MΩ 2. While 20GΩ/40GΩ ranges are enabled: Voltage Five measurement ranges 500V 4.000 MΩ/ 40.00 MΩ/ 400.0 MΩ/ 2000 MΩ/ 20 GΩ 1000V 4.000 MΩ/ 40.00 MΩ/ 400.0 MΩ/ 4000 MΩ/ 40 GΩ 8-4-1 Settings (1) To enable measurements on 20GΩ/ 40GΩ range:    1. Get the instrument into setting mode.    2.  ...
  • Page 29: Insulation Status Indicator

    8-5 Insulation status indicator 8-5-1 Reference value for insulation status, Pass/ Fail, judgement The  instrument  can  compare  the  measured  insulation  value  and  the  pre-set  reference  value  listed  below.  LCD  backlight  lights  up  and  buzzer  sounds  according to the result. This function can be turned off. With KEW 3552/ 3552BT, you can select any desired value as a reference  value; the reference values are fixed and unchangeable on KEW 3551 . ● Reference values for KEW3551 Rated voltage 100V 125V 250V...
  • Page 30: Reference Value Settings

    No“COMP”nor reference value the reference value. are displayed. (3) You can set this status indicator to ON or OFF for each range, respectively.    (The settings won t be cleared even after powering off the instrument.) [KEW3552/ 3552BT] (1) Get the instrument into setting mode.    1.   S et  the  function  switch  to  any  position  other  than  low-resistance  measurement,  and  then  hold  down  the  SETUP  button  (   2  sec.)  in  stand-by mode.    2. Use the cursor key and select the range to set the reference value. ...
  • Page 31 (2)   P ress  the  cursor  key  to  toggle  the  reference  values.  Press  the  ENTER  button  to  set  and  save  the  displayed  value  as  a  reference  value.  The  following values are selectable.  OFF, 0.100 MΩ, 0.125 MΩ, 0.200 MΩ, 0.250 MΩ, 0.400  Selectable  MΩ, 0.500 MΩ, 1.000 MΩ, 10.00 MΩ, 100.0 MΩ, Any  values (Selectable range: 0.000 MΩ ‒ 4199 MΩ) Select Any to set your desired value as a reference value:  1. Select the place of decimal point with cursor key, and press ENTER to confirm.
  • Page 32: Dar/ Pi Measurement, 1-Min Value Display (Kew3552/3552Bt Only)

    8-6 DAR/ PI measurement, 1-min value display (KEW3552/3552BT only) 8-6-1 DAR/ PI measurement and 1-min value display The instrument can measure and calculate DAR (Dielectric Absorption Ratio)  and PI (Polarization Index) values automatically during an insulation resistance  measurement. (not available on KEW3551) ●   T he  DAR  value  is  displayed  in  1  minute  and  the  PI  value  in  10  minutes  after starting a measurement.  ● The following table shows the formula and display range. Resistance value (1 min after a start of test) DAR = ...
  • Page 33: Low-Resistance Measurement (Continuity Check)

    9. Low-resistance measurement (Continuity check) # DANGER Do not apply voltage to the low resistance range. Always check the circuit or  equipment under test is surely de-energized before starting a measurement. 9-1 Zero Ω ADJ. function This function is to null the resistances (up to 3 Ω) of the test lead or internal  circuit to display the resistance of the equipment under test only.  Setting: (1) Set the function switch to V/ Ω position.  (2)   I f the instrument is in the voltage measurement mode, press the SELECT  button (< 1 sec) and switch the mode to low-resistance measurement. (3)   S hort the test leads: red lead connected to LINE terminal and black lead  connected to EARTH terminal. (4)   P ress  the  0ΩADJ  button  while  the  test  button  is  locked  or  the  remote  control switch is held. Then the LCD shows 0.00 Ω...
  • Page 34: Lcd Backlight, Led Light, Buzzer

    Fig. 9-1 ●   I f a current of 200 mA or higher is detected on the object under test, the  continuity buzzer sounds to indicate that there is continuity. If you wish to  disable  this  continuity  buzzer,  please  refer  to  10. LCD backlight, LED light, Buzzer. ●   A t  low-resistance  measurements,  impedances  of  the  operating  circuit  connected in parallel with the instrument may affect the measurement result. ● Circuit protection     T he instrument has circuit protection function: even if touching with a live  circuit  during  low-resistance  measurement  unintentionally,  the  instrument  will ...
  • Page 35: Buzzer

    10-2 Buzzer Buzzer sounds when: 1. powering on the instrument, 2. turning the function switch or pressing any button, 3. measured current is 200 mA or higher at low-resistance measurement,   (Continuity buzzer) 4. selecting 1000V range, 5. live circuit warning is activating, and 6. auto-power-off function is activated.   * For the cases 1. to 3., the buzzer can be set to always off.  10-3 Settings of backlight, LED light, and buzzer Follow  the  procedures  described  on  the  following  pages  and  change  the  settings ‒ turning on/ off ‒ of the lights and buzzer.  *   T he  procedures  depend  on  each  model.  Please  refer  to  the  explanation  about the model you re using.
  • Page 36 [KEW 3551] (1) Get the instrument into setting mode.     1.   E nsure  that  the  instrument  is  powered  off.  Hold  down  the  0ΩADJ  button.    2.   K eep  the  0ΩADJ  button  held  down,  and  set  the  function  switch  to  V/  Ω  position.  The  instrument  wakes  up  and  the  LCD  segments  start  blinking to indicate now the instrument is in setting mode.
  • Page 37 (3)   P ower off the instrument when setting completes. (The latest settings are  saved and won t be cleared even after powering off the instrument.) [KEW 3552/ 3552BT] (1) Get the instrument into setting mode.   1.   S et  the  function  switch  to  any  position  other  than  low-resistance  measurement, and then hold down the SETUP button (  2 sec.) while in  the stand-by mode.   2.   U se  the  cursor  key  and  toggle  the  screens  for  backlight  and  buzzer  setting; the following figures shows each setting screen. Backlight setting screen: The LCD shows“...
  • Page 38: Auto-Power-Off

    11. Auto-power-off To prevent the instrument being left powered on and conserve battery power,  the  instrument  automatically  turns  off  approx.  10  min.  after  the  last  switch  operation  with  audible  buzzer  sound.  To  turn  on  the  instrument,  turn  the  function switch to OFF position first, then set it to the desired range. This auto-power-off function doesn t work during a measurement or Bluetooth  data communication. (KEW3552BT only) ̶  35  ̶ 1.888.610.7664 www.calcert.com sales@calcert.com...
  • Page 39: Clock Setting (Kew3552/ 3552Bt Only)

    12. Clock setting (KEW3552/ 3552BT only) This  instrument  has  an  internal  clock  and  can  save  the  measured  data  with  time information. (Not available on KEW3551.) 12-1 Setting (1) Get the instrument into setting mode.    1.   S et  the  function  switch  to  any  position  other  than  low-resistance  measurement,  and  then  hold  down  the  SETUP  button  (   2  sec.)  while ...
  • Page 40: Memory Function (Kew3552/ 3552Bt Only)

    13. Memory function (KEW3552/ 3552BT only) This instrument can save voltage, insulation resistance, and low-resistance  measurement results in the internal memory, 1000 results max. Data can be  saved  with  two  different  site  number  for  easy  recognition.  (Not  available  on  KEW3551.) ● Data to be saved:     M easured  voltage,  insulation  resistance,  and  low-resistance,  DAR/  PI,  1-min  value,  time  and  date,  measurement  function,  and  the  data  and  site ...
  • Page 41: Recalling The Data

    (3)   U se the cursor key and  select SITE No. 1 , and  press the ENTER button to  confirm. Blink Fig. 13-2 (4)   U se the cursor key and  select SITE No. 2 , and  press the ENTER button to  confirm. Blink Fig. 13-3 (5)   U se the cursor key to select  the Data No. , and press the  ENTER button to confirm.  (Data no. is updated  automatically.) Blink Fig. 13-4 (6)   W hen data saving completes, the instrument shows stand-by screen.    Press the ESC button to modify and re-do the settings.  ● Simplified operation     Y ou  can  skip SITE  No.  1,  and  2 and Data  No. settings  and  save  the  data ...
  • Page 42: Deleting The Data

    13-3 Deleting the data (1)   H old down the MEMORY button (  1sec.) in stand-by mode, and recall the  saved data. (2)   U se the cursor key to select the data no. you wish to delete. To delete all  the  saved  data,  select ALL .  ( ALL is  displayed  between 0 and  999 .) Wishing to delete all the saved data. Fig. 13-6 (3)   T he  LCD  shows clr by  pressing  the  ENTER  button.  Another  press  of  ENTER ...
  • Page 43: Infrared Data Transmission (Kew3552/ 3552Bt Only)

    14. Infrared data transmission (KEW3552/ 3552BT only) The  internal  memory  data  can  be  transferred  to  PC  by  using  the  optical  adapter MODEL8212 USB. (Not available on KEW3551.) 14-1 How to transfer data (1)   E nsure  that  the  special  application KEW  Report has  been  installed  in  your PC. ...
  • Page 44: Bluetooth Communication (Kew3552Bt Only)

    Please  use  another  tablet  device  and  try  to  communicate  with.  If  you  still  cannot  confirm  the  connection,  there  may  be  some  problem  with  the  instrument  unit.  Please  contact your local KYORITSU distributor.  ●   T he Bluetooth word mark and logos are owned by Bluetooth SIG, Inc. and  we, KYORITSU, are licensed by them for use.  ●   A ndroid,  Google  Play  Store,  and  Google  Map  are  the  trademark  or ...
  • Page 45: Kew Smart For Kew3552Bt

    15-2 KEW Smart for KEW3552BT The  special  application KEW  Smart  for  KEW3552BT is  available  on  download  site  for  free.  (An  Internet  access  is  required.)  Please  note  that  communication charge is incurred separately for downloading applications and  using  special  features  of  them.  For  your  information, KEW  Smart  for  KEW3552BT is provided on-line only. Features of KEW Smart for KEW3552BT:  ● Remote monitoring/ checking ...
  • Page 46: Battery Replacement

    16. Battery replacement Replace  batteries  with  new  ones  when  the  battery  indicator  shows  ; battery level is almost empty.  # DANGER ● Do not open the battery compartment cover if the instrument is wet. ●   N ever attempt to replace batteries during a measurement. When opening  the battery compartment cover, ensure that the instrument is powered off  and  no  test  leads  are  connected  to,  in  order  to  avoid  getting  electrical  shock.  ●   T he  battery  compartment  cover  must  be  closed  and  screwed  before  making measurement.
  • Page 47: Shoulder Strap Belt Attachment

    17. Shoulder strap belt attachment Strap belt is supplied with this instrument to suspend from the neck to allow  both hands to be used freely for easy and safe operation.  Fig. 17-1 18. Storing in carrying case Store the instrument and test leads as the following figure shows. Test leads compartment Partition Flat test bar Unit compartment Fig. 18-1 # CAUTION ● Always power off the instrument before storing it in the carrying case. ̶  44  ̶ 1.888.610.7664 www.calcert.com sales@calcert.com...