Measurement Of The Loop Impedance - KYORITSU 4116A Instruction Manual And Users Manual

Digital psc-loop tester
Table of Contents

Advertisement

WARNING
● If the above sequence is NOT displayed or the RED LED is on for
any  reason  ,  DO  NOT  PROCEED  AS  THERE  IS  INCORRECT
WIRING. The cause of the fault must be investigated and rectified.
(3) Voltage Measurement
When the instrument is first connected to the system, it will display the
phase-neutral voltage which is updated every 1s. This mode is cancelled
whenever  the  test  button  is  pressed.  If  this  voltage  is  not  normal  or  as
expected, DO NOT PROCEED.
WARNING
● This instrument is intended only for use in single phase operation
at  230V  +10%  -15%  AC  phase  to  earth  or  for  use  in  OLD-TT
system phase to neutral.
5.2 Measurement of the Loop Impedance
(1) Set the instrument to the 200Ω or 2000Ω range.
If  the  instrument  is  set  to  the  20Ω range  slight  sparking  may  occur
when  testing  with  the  distribution  board  lead  although  the  unit  has
been designed to minimize this.
(2) Connect the lead to the instrument.
(3) Plug the moulded mains plug to the socket being tested.
(4) Check  the  LED's  are  lit  as  indicated  in  section  5.1.  If  not  DO  NOT
PROCEED - check wiring.
(5) Note the mains voltage if required.
(6) Press the "Press to Test" button. The value of loop impedance will be
displayed with the appropriate units. A bleep will sound on completion
of the test.
For best results always test on the lowest possible range.
For  example,  a  loop  impedance  measured  on  the  200Ω range  may
give an indication of 0.3Ω whereas on the 20Ω range it may read 0.28
Ω. In the event of the reading being in excess of the range (e.g. more
than 20Ω on the 20Ω range) the appropriate over-range symbol "OL"
will appear on the display. 
No harm will be done to the instrument by selecting too low a range.
― 9 ―

Advertisement

Table of Contents
loading

This manual is also suitable for:

4118a4120a

Table of Contents