8 Insulation Resistance Measurement - KYORITSU KEW3552 Instruction Manual

Insulation - continuity tester
Hide thumbs Also See for KEW3552:
Table of Contents

Advertisement

1.888.610.7664
8 Insulation resistance measurement
This instrument is used to measure insulation resistance of electric appliance 
or  circuit  to  inspect  the  insulation  performance.  Check  the  voltage  rating  of 
the  object  to  be  tested  before  making  measurement  and  select  the  voltage 
applied to. 
Note:
●   D epending  on  the  object  to  be  measured,  displayed  insulation  resistance 
value may not stabilize. 
●   T he  instrument  may  give  bleep  during  an  insulation  resistance  measure-
ment, however, this is not a malfunction.
● Measurement time may be longer when measuring a capacitive load.
●   I n  insulation  resistance  measurement,  the  earth  terminal  outputs  positive 
voltage and the line terminal negative voltage. 
●   C onnect the earth lead to the earth (ground) terminal at measurement. It is 
recommended  to  connect  the  positive  side  to  the  earth  side  when 
measuring insulation resistance against ground or when a part of the object 
under  test  is  earthed.  Such  connection  is  known  to  be  more  suitable  for 
insulation  testing  since  insulation  resistance  values  measured  with  the 
positive side connected to earth are typically less than those taken through 
the reversed connection.
# DANGER
●   B e extremely careful not to touch the tip of test probe or the circuit under 
test  to  avoid  electrical  shock  during  insulation  measurement  since  high 
voltage is present at the tip of the test probe continuously. 
  Wipe the test probe with a soft cloth, if it is wet, and use it after it s dry.
●   T he  battery  compartment  cover  must  be  closed  before  you  operate  the 
instrument.
# CAUTION
Always  disconnect  power  to  the  equipment  under  test  before  starting 
insulation  measurement.  Do  not  attempt  to  make  measurements  on  a  live 
circuit; otherwise, it may damage the instrument.
̶  20  ̶
www.calcert.com
15
10
20
5
25
0
30
sales@calcert.com