Wire Requirements
F.1 NAC Wiring
The following table lists NAC wiring requirements for the FACP.
Max.
NAC
allowable
Load
total loop
(Amps)
resistance
(ohms)
0.25
13.60
0.5
6.80
0.75
4.53
1
3.40
1.25
2.72
1.5
2.27
1.75
1.94
2
1.70
2.25
1.51
2.5
1.36
2.75
1.24
3
1.13
Calculations are based on Direct-Current Resistance data for uncoated copper wire, per
National Electrical Code (2005 Edition) Table 8, Conductor Properties.
122
CLASS-B
Max. allowable wire pair length
(feet)
AWG 12
AWG 14
AWG 16
solid
solid
solid
3523
2215
1391
1762
1107
695
1174
738
464
881
554
348
705
443
278
587
369
232
503
316
199
440
277
174
391
246
155
352
221
139
320
201
126
294
185
116
Table F.2 NAC Wiring Requirements for FACP
Max. allowable wire pair length
AWG 18
AWG 12
AWG 14
solid
solid
solid
875
1762
1107
438
881
554
292
587
369
219
440
277
175
352
221
146
294
185
125
252
158
109
220
138
97
196
123
88
176
80
160
101
73
147
RP-2001 Series Manual — P/N 52985:D5 1/26/2017
NAC Wiring
CLASS-A
(feet)
AWG 16
AWG 18
solid
solid
695
438
348
219
232
146
174
109
139
88
116
73
99
63
87
55
77
49
111
70
44
63
40
92
58
36