F.1 NAC Wiring
The following table lists NAC wiring requirements for the FACP.
Max.
allowable
NAC Load
total loop
(Amps)
resistance
(ohms)
0.25
13.60
0.5
6.80
0.75
4.53
1
3.40
1.25
2.72
1.5
2.27
1.75
1.94
2
1.70
2.25
1.51
2.5
1.36
2.75
1.24
3
1.13
Calculations are based on Direct-Current Resistance data for uncoated copper wire, per
National Electrical Code (2005 Edition) Table 8, Conductor Properties.
RP-2002 Series Manual — P/N 53039:E6 1/26/2017
CLASS-B
Max. allowable wire pair length
(feet)
AWG 12
AWG 14
AWG 16
solid
solid
solid
3523
2215
1391
1762
1107
1174
738
881
554
705
443
587
369
503
316
440
277
391
246
352
221
320
201
294
185
Table F.2 NAC Wiring Requirements for FACP
Max. allowable wire pair length
AWG 18
AWG 12
solid
solid
875
1762
695
438
881
464
292
587
348
219
440
278
175
352
232
146
294
199
125
252
174
109
220
155
97
196
139
88
176
126
80
160
116
73
147
Wire Requirements
CLASS-A
(feet)
AWG 14
AWG 16
AWG 18
solid
solid
solid
1107
695
554
348
369
232
277
174
221
139
185
116
158
99
138
87
123
77
111
70
101
63
92
58
438
219
146
109
88
73
63
55
49
44
40
36
151

Hide quick links: