Master Programming Level
 medical alert
 combo autoresettable
The auto-silence feature can be enabled or disabled. If this feature is enabled, the alarm signals will be turned off after 20 minutes of
activation
The installer must write in the Date of Final Assembly on the Master Marking and Warranty label, located on the FACP backbox
door

Charger Disable

Pressing 3 while viewing System Setup Screen #2 will allow the programmer to enable or disable the onboard battery charger. If an
external battery charger is being used, the onboard battery charger must be disabled. Each press of the 3 key will toggle between Chrgr
Disable No and Chrgr Disable Yes.
3.5.5 Option Modules
PROGRAMMING
1=SYSTEM SETUP
2=OPTION MODULES
3=HISTORY
Programming Screen #2

ANN-BUS

Pressing 1 while viewing the Option Modules screen will cause the control panel to display the following screens.
1=BUS ENABLED
2=BUS MODULES
3=AUTO CONFIGURE
A variety of ANN-BUS option modules can be installed in the FACP. These devices communicate with the FACP over the ANN-BUS
terminals on the control panel.
ANN-BUS Enabled
The ANN-BUS must be enabled if any modules are installed on the ANN-BUS terminals. To enable the ANN-BUS, press 1 while view-
ing ANN-BUS screen #1 so that the display reads ANN-BUS Enabled Yes. Each press of the 1 key will cause the display to toggle
between ANN-BUS Enabled Yes and ANN-BUS Enabled No.
BUS Modules
If an ANN-BUS module is installed, press 2 while viewing ANN-BUS screen #1 to select ANN-BUS addresses for the module(s). The
following screen will be displayed.
Pressing the down arrow key will allow the programmer to view additional screens displaying Addresses 1 - 8. Pressing the number cor-
responding to the desired address will display a screen with technical information about the selected module.
In the technical information screen, pressing 1 for Type will display the following screens:
ANN-BUS MODULE TYPE
1=NOT INSTALLED
2=ANN-80
3=ANN-I/O
Press the number corresponding to the module type, if any, that is installed with the selected address. This will enable the module.
MS-5UD & MS-10UD Series Manual — P/N 52626:C7 6/12/2018
Options available for the FACP include annunciators, printer connection for acquiring hardcopy printouts
of panel data and onboard DACT.
Pressing 2 while viewing Programming Screen #2 will display the following screen:
ANN-BUS
NO
ANN-BUS Screen #1
1=ADDR. 1
2=ADDR. 2
3=ADDR. 3
Module Type Screen #1
OPTION MODULES
1=ANN-BUS
2=ON BOARD DACT
ANN-BUS
1=ANN-S/PG OPTIONS
2=ANN-80 OPTIONS
3=ANN-RLY OPTIONS
ANN-BUS Screen #2
ANN-BUS MODULES
NONE
NONE
NONE
On Board DACT Screen #1
ANN-BUS MODULE TYPE
1=ANN-S/PG
2=ANN-RLY
3=ANN-LED
Module Type Screen #2
ANN-BUS
1=ANN-AUDIO OPTIONS
2=ANN-SEC ENABLE
NO
ANN-BUS Screen #3
ANN-BUS MODULE TYPE
1=ANN-AUDIO MODULE
Module Type Screen #3
Programming
71