8 Starting/Stopping
the MV Station will turn to the OPERATION mode and feed the generated AC current to
the grid.
MV Station needs no manual control in daily operation. Only qualified
personnel are allowed to open the cabinet door for maintenance or
troubleshooting.
Keep the door closed and locked and store the keys of the door by appointed
personnel during normal operation.

8.2 Stopping

Stop the MV Station when maintenance and service work is required or a fault occurs.

8.2.1 Normal Stop

Proceed as follows to stop the MV Station during normal maintenance and service work
as follows:
step 1 Stop the MV Station through the stop instruction on the LCD panel.
step 2 Disconnect the DC side and auxiliary power supply switches.
step 3 Disconnect the MV Station downstream switches.
step 4 Disconnect the MV Station upstream switches.
step 5 MV Station stops running.
- - - - E E n n d d

8.2.2 Stop in Case of Fault

Proceed as follows to stop the MV Station when a fault or emergency occurs as follows:
step 1 Press the emergency stop button.
step 2 Disconnect the auxiliary power supply switches.
step 3 Disconnect the MV Station downstream switches.
step 4 Disconnect the MV Station upstream switches.
step 5 MV Station stops running.
- - - - E E n n d d