Appendix 4.6 Parts for EMC Measures

Appendix 4.6.1 Shield Clamp Fitting

The ground can be directly connected to the grounding plate as shown below to increase the effect.
Install the grounding plate near the outlet (within 10cm) of each panel, and press against the grounding
plate with the clamp fitting. If the cables are thin, several can be bundled and clamped together.
To provide sufficient frame ground, install the grounding plate directly on the cabinet or connect with a
grounding wire.
If the grounding plate and clamp fitting set AERSBAN- SET is required, please contact Mitsubishi.
• Outline drawing
AERSBAN-DSET
AERSBAN-ESET
Downloaded from
ManualsNet.com
APPENDIX 4 EMC INSTALLATION GUIDELINES
Appendix 4.6 Parts for EMC Measures
Grounding plate
2-ø5 hole
Installation
hole
Note 1)
M4 screw
a
b
100
86
70
56
search engine
Clamp fitting
(Fitting A, B)
Clamp section drawing
(Note 1) Screw hole for wiring to cabinet's grounding plate.
(Note 2) The grounding plate thickness is 1.6mm.
c
Enclosed fitting
30
Two A clamp fittings
One B clamp fitting
I-230
Peel the cable sheath
at the clamp section
Cable
Grounding
plate
Cable
Shield sheath
Clamp fitting
Max. L
Unit: mm
L
A clamp fitting
70
B clamp fitting
45