Proline Edition X cooling thermostats
9.2.4 Device data
Master
Command
T ext Pt
T ext analog
T ext serial
T cont. head 39.80 Level
T heatsink
Pump pow.
Pump rpm
Pumpe cur.
Pump
Menu
9.2.5 Fault memory
For the analysis and localization of faults the Command version includes a fault memory in which up to
45 fault and alarm messages are saved.
Command
No. Source Code Type Date
10 Safety 2 Alarm ------------ -----------
9 Safety 4 Warn. 28.08.03 15:32:02
8 Contro. 32 Error
7 Contro. 3 Warn. 06.06.03 11:15:11
6 Contro. 9 Alarm 05.06.03 08:45:01
5 Contro. 3 Alarm 01.06.03 17:58:22
4 Contro. 4 Warn. 28.05.03 20:01:22
3 Contro. 5 Warn. 27.05.03 07:58:00
Low level
Pump
Menu
YACE0100 / October 4, 2018
25.70 Tint
---.-- Mains U(%) 100.74
---.-- Mains frequ.
51.68 Low voltage 27.90
44.90 5V supply
5460 Fan voltage
1.68 Cur. cons.
End
T
set
17.07.0310.:52:02
End
T
set
Maintenance
MNEmv ShoWX
Various device datas are displayed.
Device data
-8
Device data
50
T ext shows various actual temperatures
4
in °C from ext. Pt100 and the modules.
T cont. head and T heatsink are
5.00
temperatures of electronics in the Master
7.0
in °C.
2.84
Pump power in Watts, speed in rpm,
current in ampere (A).
T
int
temperature in °C.
T
fix
Mains voltage in percentage (%) of
nominal and frequency in hertz (Hz).
Level indicates the liquid level in the
internal bath.
Voltage of power transformer, 5 V supply
and fan in Volt.
Cur. cons.: Mains current consumption in
Ampere.
Error store
Time
Settings
store
The last message is at the top.
Each message line can be marked with
the cursor keys. The message appears in
plain text in the footer.
Under Source the CAN node is displayed
which signaled the fault.
Code is the number, which in the Master
is shown in the display until the cause
has been rectified.
T
fix
Type: Alarm, Warning or Fault (Error).
( Section 7.5)
Settings
Device status
Display
indicates the current internal bath
Device status
Display
.
Error
101