9: 300 Series Addressable Devices; Slc Capacity; Slc Performance; Surge Suppression - Honeywell SLC Installation Manual

Intelligent control panel
Table of Contents

Advertisement

SLC Capacity

1.4.9 300 Series Addressable Devices
Fire•Lite's 300 Series of addressable devices are fully compatible with the MS-9200, MS-9200UD,
MS-9200UDLS, MS-9600, MS-9600LS(C/E), MS-9600UDLS/E, and MS-9050UD FACPs. The
devices must be configured for CLIP (Classic Loop Interface Protocol) Mode operation. The
address of 300 series devices cannot be set above 99. Compatible devices include:
• SD300 Photo
• SD300T Photo w/Thermal
• CP300 Ionization
• BG-10LX Pull Station
1.5 SLC Capacity
The protocol selected for an SLC loop determines the maximum number of devices that can be
handled by the loop. See Section 1.3, "Polling Protocols", on page 10. Within those limits, the
individual control panel may have additional restrictions. See the specific installation manual for
this information.

1.6 SLC Performance

SLC performance depends on the type of circuit (Style 4, Style 6, or Style 7) and the components
on the circuit.
NOTE: SLC operation meeting Style 7 requirements isolates each device on the SLC from faults
that may occur within other areas of the SLC.
Wiring style requirements are determined by national and local codes. Consult with the Authority
Having Jurisdiction before wiring the SLC. The table below (derived from NFPA 72-1999) lists
the trouble conditions that result when a fault exists on an SLC.
Type of Fault
Single Open
Single Ground
Short
Short and open
Short and ground
Open and ground
Communications loss
• Trouble - The control panel will indicate a trouble condition for this type of fault.
• Alarm - The control panel must be able to process an alarm input signal in the presence of this type of fault.

1.7 Surge Suppression

One primary surge protector must be used with each SLC wiring pair whenever SLC wiring runs
outside the building. For detailed information refer to "Surge Suppression" on page 71.

1.8 LED Operation

The table below lists the LED operation on the various devices on an SLC.
FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014
• M300 Monitor Module
• M301 Mini Monitor Module
• M302 2-wire Monitor Module
• C304 Control/Relay Module
Style 4
Trouble
Alarm, Trouble (ground)
Trouble
Trouble
Trouble
Trouble
Trouble
Table 1.2 SLC Performance
Device
Monitor Module
Blinks RED
Control Module
Blinks GREEN
Detector
Blinks RED
Table 1.3 LED Operation
Style 6
Alarm, Trouble
Alarm, Trouble (ground)
Trouble
Trouble
Trouble
Alarm, Trouble
Trouble
Standby
Activated
Steady RED
Steady GREEN
Steady RED
Introduction
Style 7
Alarm, Trouble
Alarm, Trouble (ground)
Alarm, Trouble
Trouble
Alarm, Trouble
Alarm, Trouble
Trouble
13

Hide quick links:

Advertisement

Table of Contents
loading