Wiring Specifications - Honeywell Silent Knight SKE Series Installation And Operation Manual

Voice evacuation
Table of Contents

Advertisement

3.4.2

Wiring Specifications

The maximum line resistance of the wire run from FACP to voice evacuation control system is
50W. All wiring and devices installed in the system must meet the standards described in
National Electrical Code (NFPA 70), NFPA Standard 72, and Life Safety Code (NFPA 101).
To avoid induced noise (transfer of electrical energy from one wire to another), keep input
wiring isolated from high-current output and power wiring. Avoid pulling one multiconductor
cable for the entire panel. Instead, separate the wiring as follows:
1/4" spacing must be maintained
between each of these circuit types;
as well as between power limited
and non power-limited circuits.
DO NOT pull wires from different groups through the same conduit.
For the same reasons, wiring within the cabinet should be routed around the perimeter of the
cabinet. It should not cross the printed circuit board where it could induce noise into the
sensitive microelectronics or pick up unwanted RF noise from the high speed circuits.
High frequency noise, such as that produced by the inductive reactance of a speaker or bell,
can also be reduced by running the wire through ferrite beads or by wrapping it around a
ferrite toroid core. Figure 3-5 provides an example.
CMD Inputs
151267
Table 3-6
Input/Output Type
Non Power-Limited:
Power-Limited:
Audio:
To AC
Battery Cable
Figure 3-5 Wire Routing Example
firealarmresources.com
Wiring
AC power, Standby batteries
Notification devices, SKE-SRM, and Relays
Speaker
Installation
Speaker
Speaker
3-9

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ske-450Ske-450-zn4Ske-450-zn6

Table of Contents