Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x

System properties (settings)

Figure 30. Win512 version 2.7.x "System" dialog box.
NOTE! Default settings in Win512 version 2.7.x are shown but
might vary depending on convention.

System data

Logical name

Normally not changed but each system can have a unique name.

Alarm delay time

The fire alarm delay time is set here for the detectors with this option
selected via Win512. Default is "0" and up to 127 seconds can be set.
NOTE! This delay starts when the alarm normally should have been
activated, i.e. it will be added to all other delay times (e.g. after an L-
/N-/H-35 algorithm).
In the Australian and New Zealand conventions will the "Alarm
Verification Facility be valid when "Delayed alarm" is selected for a
conventional zone line input.
Facility", page 96.

Main power loss fault delay time

A fault will be activated 30 minutes (default) after loss of mains (230
V AC). 0 – 300 minutes can be set.

Alarm reset

One of the following alternatives can / shall be selected.
133
See chapter "Alarm Verification