Daylight Saving Time; Loss Of Main Power Source; Fault: Loss Of Main Power Source; Lcd Backlight - Panasonic EBL512 G3 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL512 G3:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01472
Rev: -
16.28.1
16.29
16.29.1
16.29.2
16.30
Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x

Daylight saving time

The time is automatically changed when the Daylight saving time
period starts and stops respectively, if set so in Win512 version 2.7.x.
When, is depending on which convention that is used:
 Australian convention: Forward 1 hour the first Sunday in
October, 02:00  03:00. Backward 1 hour the first Sunday in
April, 03:00  02:00.
 New Zealand convention: Forward 1 hour the last Sunday in
September, 02:00  03:00. Backward 1 hour the first Sunday
in April, 03:00  02:00.
 All other conventions: Forward 1 hour the last Sunday in
March, 02:00  03:00. Backward 1 hour the last Sunday in
October, 03:00  02:00.

Loss of main power source

Regarding the Main power source and Second power source, see
chapter "Power supply", page 152.

Fault: Loss of main power source

The delay time for the fault "Loss of main power source" can be set
(in Win512 version 2.7.x) to 1 – 300 minutes. (A delay time > 30
minutes is a violation to the EN54-2 standard.

LCD backlight

In order to reduce the current consumption the LCD backlight will
never be turned on during loss of the main power source.

Evacuate

When the soft key "Evacuate" (P7)
programmed for sounders (i.e. type "Alarm devices"), will be
collectively turned ON (steady). This is indicated in the LCD:
Evacuate in progress
The sounders will remain turned ON until they are turned OFF by
pressing the soft key "Evacuate off" (P7).
NOTE 1! The alarm devices (sounders) will always be activated
steady (sound continuously) irrespective of the fact that the outputs
can be set to anything else for fire alarm (e.g. intermittent).
107
The soft key "Evacuate" is only visible / valid for the Belgian, British
Standard, Hungarian, Spanish and Ukrainian conventions.
108
Alt. when a programmable input is activated. One input per c.i.e.
109
Alt. when the programmable input is de-activated.
109
107
108
is pressed
, all outputs
109

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents