Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
Control unit outputs S0 – S3
Each control unit has four programmable, supervised (monitored)
voltage outputs:
S0
Supervised (monitored) voltage output, 24V DC, max. 500 mA
(Fuse F4)
S1
Supervised (monitored) voltage output, 24V DC, max. 500 mA
(Fuse F5)
S2
Supervised (monitored) voltage output, 24V DC, max. 500 mA
(Fuse F6)
53
S3
Supervised (monitored) voltage output, 24V DC, max. 500 mA
(Fuse F7)
Connections and more information, see dwg. 512 G3 - 23.
Control unit outputs R0 & R1
Each control unit has two programmable relay outputs. Relay contact
ratings: 30 V, 1A.
R0
Relay output, NO or NC contacts programmable
R1
Relay output, NO or NC contacts programmable
Connections and more information, see dwg. 512 G3 - 23.
8 relays expansion board 4581 Output 0 –
Output 7
NOTE! This board has to be programmed in Win512 version 2.7.x as
a 1581 board.
Each 4581 board has eight programmable relay outputs:
Output 0
Relay output, NO or NC contacts programmable
Output 1
Relay output, NO or NC contacts programmable
Output 2
Relay output, NO or NC contacts programmable
Output 3
Relay output, NO or NC contacts programmable
Output 4
Relay output, NO or NC contacts programmable
Output 5
Relay output, NO or NC contacts programmable
Output 6
Relay output, NO or NC contacts programmable
Output 7
Relay output, NO or NC contacts programmable
Relay contact ratings: Max. 2A @ 30 V DC.
52
This is default, but via Win512 version 2.7.x it is possible to set each
output individually as not supervised (not monitored). A normally high
output is not supervised.
outputs", page 105.
53
Note! This output will be low in case of system fault (via the watch dog
reset circuit). May be used as a supervised voltage output for fault warning
routing equipment (Fault tx).