Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
Alert Annunciation function, see chapter "Alert Annunciation", page
97.
1735 Alert Annunciation Unit (AAU). A compact size enclosure
(HxWxD, 145 x 220 x 50 mm) made of grey high impact ABS.
Fitted with a supplementary "O" ring gasket, it will comply
with IP61, in respect of dust and moisture. The unit has no
door, i.e. the front is accessed directly but the push buttons are
disabled until they are supposed to be used. The unit shall be
wall mounted. Two compression glands are attached. The
front's designation texts are in Swedish.
All or selected fire alarms will be presented in a display
(alphanumeric LCD, 2x40 characters), with back-light.
alarm text will also be presented together with each alarm, if
programmed in Win512 version 2.7.x. Furthermore, at least
617 texts can for selected fire alarms be stored in the unit and
will in such a case be shown, instead of the texts sent out from
EBL512 G3 for these alarms. These text messages will be
downloaded to the unit via Win512 version 2.7.x. A built-in
buzzer will sound to indicate a not acknowledged AA alarm.
New software versions can be downloaded directly in the unit.
The unit is power supplied from EBL512 G3 or an external
power supply.
The unit has the following LEDs:
Fire and Alarms queued, indicating fire / AA alarm.
Operation, indicating that the unit is in operation, i.e. the AA
function is enabled in the system. A time channel can be used
to enable the AA function.
Fire brigade alerted, indicating that the "Fire brigade tx"
output is activated in EBL512 G3 because:
- the activated fire alarm is not an AA alarm
- the AA function has been ended, e.g. the acknowledge or
investigation time respectively has run out, etc.
Acknowledge, indicating that the AA alarm has been
acknowledged.
The unit has the following push buttons:
Alarms queued, used to scroll amongst the alarms.
Acknowledge, used to acknowledge an AA alarm and hereby
also silence the buzzer.
Reset, used to reset an AA alarm.
The unit shall run in S/W mode 1735 – 1587. Up to 1200 m
cable can be used.
description MEW00224.
1736 Alert Annunciation Unit (AAU). This unit is like 1735, except
it has a neutral front, where the designation texts, in any
language, are made separately and by production put into a
transparent "text slot" for the LED and push button respectively.
For more information, see Technical
55