Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x

Redundancy in distributed system

In a distributed system (i.e. two or more control units in a TLON
network), with fire alarm routing equipment in only one of the control
units, it is possible to indicate fire alarm and to activate the output for
fire alarm routing equipment (fire brigade tx) even in case of a single
open circuit (cut-off) or single short circuit in the TLON network.
EBL512 G3 units with the S/W EBL512 G3 United version 2.7.x
makes it possible to use EBL512 G3 units (5000 / 5001) together with
EBL512 units (1548 / 1549 / 1550), in a TLON Network, i.e. a mixed
system.
NOTE!
This function is only valid for the non-programmable standard output
for fire alarm routing equipment (fire brigade tx). The programmable
outputs have no benefit of this function.
(commissioner) should for any output, avoid such control expression
(trigger conditions) that for the correct function is dependent on no
fault on the TLON network.
There are two ways of system build-up:
 Master and slaves individually connected to the master.
 Master and several control units connected in parallel and
connected to one input in the master.
NOTE! An EBL512 G3 control unit cannot be the master

Master and Slaves

Master
Slave
Fire brigade tx
output and
routing equipm.
1580
Figure 25.
Master and slaves.
connected to the master's 1580 board(s) and/or 3361 unit(s).

Master unit

The control unit containing the fire alarm routing equipment is called
the "Master" and has to be an EBL512 unit (cannot be an EBL512
112
TLON
Slave
Fire brigade
tx output
Each slave is individually
The system planner
Fire brigade
tx output