Cyber Sensor Functions - Panasonic EBL512 G3 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL512 G3:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01472
Rev: -
19
Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x

Cyber sensor functions

The latest generation of detectors are called "Cyber sensors".
The Cyber sensor "family" consists of the following detectors:
 Conventional photoelectric smoke detector 4352
 Conventional multi detector 4350
 Analog photoelectric smoke detector 4301
 Analog multi detector 4300
NOTE! NOTE! NOTE! NOTE! NOTE! NOTE! NOTE!
The analog detectors 4301 and 4300 can via the address setting tool
3314 be set in different modes. In EBL512 G3 can NORMAL mode
be used for both types but the 2312 mode only for 4301. See chapters
"COM loop units", page 37 and "Functions / Services / Features",
page 84, i.e. the analog detectors 4301 and 4300 do not use the cyber
sensor functions described below.
The conventional detectors 4352 and 4350 uses some of the cyber
sensor functions. See the function respectively below.
The AI function is used to secure the real fire alarms but also to
reduce the false (nuisance) alarms with up to 46 %. The AI function
is depending on if the detector is a photoelectric smoke detector (4352
/ 4301) or a multi detector (4350 / 4300):
Combined heat and smoke sensing will guarantee reliable and
accurate fire alarm detection, e.g. by shortening the delay time
and/or raise the sensitivity (i.e. lower the alarm threshold level).
Variable delay time. The delay time is influenced by the
temporary temperature and/or smoke obscuration changes just
before and after the alarm threshold level was passed. The
delay time before a fire alarm is activated can be shortened up
to 50 % (e.g. from 20 to 10 sec.), or the delay time can be
extended in order to reduce false (nuisance) alarms.
Learning function / conditions. The detector will adapt a
learning condition depending on the long-time influence of
smoke and/or the temperature where the detector is located.
122