Multi Detectors' (3316 And 4300 + Decision Algorithm); Properties - Panasonic EBL512 G3 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL512 G3:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01472
Rev: -
21.6.3
L-15
Offset,
18
Smouldering
Offset,
26
Pre-warning
Offset,
36
Fire alarm
Level,
150
Heavy alarm
Step
6
A
value
21.6.4
Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
Smoke detectors' (3304, 4301, 3316 and 4300)

properties

Detector:
3304 / 4301(OPT)
3316 / 4300 SMOKE (AMD), i.e. the smoke detector part
when decision algorithm is not selected.
Logical name: L-15 Low sens. 15s, L-35 Low sens. 35s, N-15
Normal sens. 15s, N-35 Normal sens. 35s, H-15 High sens. 15s and H-
35 High sens. 35s.
Short name: L-15- L35, N-15, N-35, H-15 and H-35.
Algorithm parameters: Default values, see table:
3304 / 4301
(OPT)
L-35
N-15
N-35
H-15
18
15
15
12
26
22
22
18
36
30
30
24
150
150
150
150
2
5
2
4
NOTE! If any of these values are changed, it might be a violation
to the EN54-2 standard.
A
The "Step value" is used in the alarm algorithm.

Multi detectors' (3316 and 4300 + decision algorithm)

properties
Detector:
3316 / 4300 SMOKE (AMD), i.e. the 3316 detector when
decision algorithm is selected.
Logical name: Decision algorithm
Short name: Dec (Shown in menu H4/U5.
Algorithm parameters: Default values, see table:
3316 / 4300
SMOKE
Offset,
(AMD)
50
Smoke Pre-
Offset,
warning
58
Smoke alarm
Level,
50
Heat Pre-warning
Level,
58
Heat alarm
139
3316 / 4300 SMOKE
(AMD)
H-35
L-15
L-35
N-15
12
18
18
15
18
26
26
22
24
36
36
30
150
120
120
120
2
12
4
10
N-35
H-15
H-35
15
12
12
22
18
18
30
24
24
120
120
120
4
8
4