Panasonic EBL512 G3 Planning Instructions page 148

Fire alarm system
Hide thumbs Also See for EBL512 G3:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01472
Rev: -
Ohm
45
40
35
30
25
20
15
10
5
0
Figure 32. Graphs showing the total conductor resistance in relation to the
COM loop units' total current consumption. NOTE! The graphs start at "0
mA" but graph 1 ends at "320 mA" and graph 2 ends at "350 mA". End of
graph = max. allowed loop current. (42.3 ohm = 863 m cable length.)
Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
Maximum conductor resistance
40
80
120
Total COM loop unit current consumption
NOTE! The graphs are valid for the cable type ELQYB 2 x 1 mm
2
(0.75mm
) with the conductor resistance 24.5 ohm / km. The total
conductor resistance (ohm) = L conductor (ohm) + C conductor
(ohm).
146
2 x 1 mm (0.75 mm
24.5 ohm / km
160
200
240
2
)
280
320
mA

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents