Logic; Supervised / Not Supervised; Time Activation Output - Panasonic EBL512 G3 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL512 G3:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01472
Rev: -
13.2
13.3
13.4
Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x

Logic

(•) Normally open / low Normally open relay contact or normally
60
low voltage output.
( ) Normally closed / high Normally closed relay contact or
normally high voltage output (24V DC).

Supervised / Not supervised

A voltage output is supervised (default).
"Supervised" checkbox the voltage output will be not supervised.
A normally high output cannot be supervised.

Time Activation Output

Each output uses an "Time Activation Output", which controls the
output's activation. The following are available:
No. 1 is default Steady / Continuous. No. 2 is default intermittent
0.8/0.8s. No. 3-8 can be built up with type and time.
Types:
0. Steady (continuous)
1. Intermittent
2. Pulse
3. Steady, Delayed Activation
4. Intermittent, Delayed Activation
5. Pulse, Delayed Activation
6. Steady, Delayed De-Activation
60
The logic is set in the Win512 version 2.7.x dialog box "Voltage / Relayed
Output".
61
The logic is set in the Win512 version 2.7.x dialog box "Voltage / Relayed
Output". NOTE! A normally high output can not be supervised and it will
be low for a few seconds during restart of the c.i.e.
61