18.1.2.1
Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
The outside switch is turned OFF (i.e. from activated to not
activated state).
 "FAULT:
FB
114
Serviced.
 Any fire alarm ("ALARM") and acknowledged alarm
("ACKNOWLEDGED") will automatically be disabled /
isolated. (I.e. it has to be re-enabled via menu H2/ B5.)
Indicated by LED "General disablements" on the c.i.e. front.
 Any fire alarm ("ALARM") and acknowledged alarm
("ACKNOWLEDGED") will automatically change the state
to "Isolated alarm" (see below) and in the fire alarm list
(presented in the display) "ALARM" or "ACKNOWLEDGED"
will be replaced with "ISOLATED".
An example:
ISOLATED alarm
Zone
002-03
User definable alarm text for 002-03.
Menu
Isolated alarm
A fire alarm will automatically change state to "Isolated alarm" when
the "outside switch" (see above) is turned off, i.e. when it is not
activated any more (see above).
The following is valid for an isolated alarm.
 LEDs "Fire" (on the c.i.e. front) not activated.
 The c.i.e. built-in buzzer not activated.
 Presented as isolated alarm, see the example above
(ISOLATED ......).
 Programmable outputs not activated.
114
Since this fault is always latched, it has to be acknowledged via menu H6.
119
Silence
switch
Alarm number 1 (of 1)
Address
active
"
will be