Analog Sensor Bases (ASB)
An analog detector (Sensor) shall be plugged in an analog base. The
COM loop address is set in the detector, see below.
22
3312 Analog Base.
and an ext. LED (2218). Prepared for mechanical lock of the
detector - if required. Recess for label holder (3391). The base
has an address label on which the plugged-in detector's COM
loop address can be written.
3313 Analog Base. Like 3312 but instead of screw terminals for the
COM loop and an ext. LED this base has fast connectors (blue
and grey respectively.
3314 Analog Base. Like 3312FL but no connector (grey) for an ext.
3312F
LED.
4313 Analog Base with isolator. An analog detector (Sensor) is to be
plugged in 4313. Terminals for an ext. LED (2218). Prepared
for mechanical lock of the detector - if required. Recess for
label holder (3391). It has also a built-in short circuit isolator
(see page 49). The isolator's COM loop address is set with the
Address setting tool (3314). The base has an address label on
which both the plugged-in detector's COM loop address and the
isolator's COM loop address can be written.
The Address setting tool (3314) is also used for mode setting:
NORMAL mode: Used for 4313 in system EBL512 G3.
2330 mode: Used for EBL512 G3 United version 2.7.x in a
mixed system.
2312 mode: Not used in a mixed system.
Addressable Manual Call Points
3333 Addressable Manual Call Point.
A built-in LED will indicate that fire alarm is generated, i.e. the
glass is broken.
supplied test key, without breaking the glass.
polycarbonate flap is protecting the glass. The COM loop
address is set with the Address setting tool (3314).
3333 is to be surface mounted in the supplied red back box or
flush mounted on a Swedish 65mm circular mounting box.
For indoor use and in dry premises.
The Address setting tool (3314) is also used for mode setting.
NORMAL mode: Flashing or not flashing LED (see Product
leaflet MEW00097) is set via Win512 version 2.7.x.
2330 mode: "2333 mode" and "flashing LED mode".
2312 mode: "2333 mode" and "non-flashing LED mode".
22
This base will be replaced by 3312FL and 3312F.
23
The manual call points have a response time < 5 s.
3312 has screw terminals for the COM loop
23
3333 conforms to EN54-11.
Routine testing can be performed with a
40
A hinged