Input Programming; Trigger Conditions - Panasonic EBL512 G3 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL512 G3:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01472
Rev: -
11
11.1
Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x

Input programming

Input programming is done in Win512. For more information see
Win512 help. Each input has to have an individual Trigger condition
("Triggered by") and Logic. It is not allowed to let two or more inputs
have the same trigger condition.

Trigger conditions

The following trigger conditions are available:
0. Not used
1. Alarm Key Cabinet (one input per control unit)
2. Alert Annunciation Acknowledge
3. Alert Annunciation Reset
4. Fault Signal External Power Supply (one input per control unit)
5. Fault Signal External Fuses (one input per control unit)
6. Time Channel 15 - 63 (one input per time channel per system)
7. General Fire (max. 127 per C.U.)
8. Activated Routing Equipment (one input per C.U.)
9. Activated Extinguishing (one input per C.U.)
10. Activated Fire Ventilation (one input per C.U.)
11. External Fault (50 inputs per system)
12. Extinguishing start
13. Extinguishing stop
14. Interlocking input (200 inputs per C.U. / 1000 per system)
15. Loss of main power source to external power supply (one input
per C.U.)
16. Loss of battery charger to external power supply (one input per
C.U.)
17. Door Closing Test Input
18. Pre-warning Input (input and corresponding fire alarm input
"connected" to the same C.U.)
19. Evacuate (one input per C.U.)
20. Activate output
21. Extinguishing alarm
49
25. Alarm from CU
26. Silence alarms (one input per system)
49
99. Zone Line Input
48
All inputs and outputs involved have to be connected to the same c.i.e.
49
Only valid for the Addressable multipurpose I/O unit 3361, Input 0, used
as zone line input (Z).
48
48
61

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents