Panasonic Eco Solutions Nordic AB
MEW01472
Rev: -
3
3.1
3.1.1
3.1.2
3.1.3
Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x

Overview

The EBL512 G3 system

EBL512 G3 is a microprocessor controlled intelligent fire alarm
system, intended for analog addressable smoke detectors, as well as
conventional detectors and manual call points. Programmable control
outputs and output units are available. In EBL512 G3 United version
2.7.x, up to 512 addresses can be connected to each control unit (c.i.e.)
- according to EN54-2.
EBL512 G3 is available in several types, versions and configurations.
It can be connected to a TLON network, i.e. in a "system" with up to
30 control units. Each control unit has access to all information.
Product type no. Product name
5000
EBL512 G3 c.i.e.
With front and display.
5001
EBL512 G3 c.i.e.
Without front, display and printer. No door.
EBL512 G3 is designed according to the European standard EN54,
part 2 and 4. The Swedish front conforms to SS3654.

Printer

The control unit EBL512 G3 type 5000 can be delivered with a printer
("PRN" included in the article number) or without a printer.
In Ext. Fire Brigade Panel 1826 it is possible to mount an optional
Printer 1835.

Expansion boards

In the control unit (c.i.e.) it is possible to mount up to six expansion
boards. The following types are available:
Product type no. Product name
4580
8 zones expansion board
4581
8 relay outputs expansion board
Regarding the expansion boards, see also chapter "Expansion boards
458x, page 27 and EBL512 G3 drawings.

Power supply

The main power source is a built-in switched power supply (rectifier)
5037. 230 V AC, 1.6 A / 24 V DC, 6.5 A.
The second power source is a backup battery (2 x 12 V). In the c.i.e.
4
Printer 5058 is a spare part for the c.i.e. type 5000 with a printer, i.e. it
comes without a mounting frame etc.