28
Device Description
Table 15: EMc – Testing Standards: Emission of Interference
Standard
• EN 55032 Class B
*)
QP = Quasi Peak Detector; AV = Average Detector
**)
If necessary, please find different data in the section "Approval" (regarding approval for EMC A or
EMC B).
Manual
Version 1.0.1
750-600/040-001 End Module with Potential Group XTR
Test Value
40 dB(μA) ... 30 dB(μA) QP,
0.15 MHz ... 0.5 MHz
30 dB(μA) ... 20 dB(μA) AV,
0.15 MHz ... 0.5 MHz
30 dB(μA) QP, 0.5 MHz ... 30 MHz
20 dB(μA) AV, 0.5 MHz ... 30 MHz