Commissioning
6.2 PROFINET IO
6.2.2

Configuring by means of GSD file

Introduction
The GSD file allows you to configure the ET 200M using STEP 7 V5.4, Service Pack 2 or higher.
To do so you must install the GSD in the configuration software beforehand.
Requirements
You will need a GSD file, available for download from the Internet
(http://support.automation.siemens.com/WW/view/en/25057900).
Interface Module IM 153-4 PN:
GSDML-V1.0-Siemens-ET200M-"date in yyyymmdd format".xml
Configuring the ET 200M on PROFINET IO with STEP 7
1. Start STEP 7 and then select the Tools > Install New GSD file menu command in HW
Config.
2. Select the GSDML file to install from the next dialog box, then confirm with OK. Result: The
ET 200M appears in the PROFINET IO folder of the hardware catalog.
3. For additional information, refer to the STEP 7 Online Help.
6.2.3

Assigning device names to the I/O device

Introduction
Each PROFINET IO device is assigned a unique device ID at the factory (MAC address).
For configuration and in the user program, each ET 200M IO device is addressed with its
device name.
For detailed information on addressing in PROFINET IO, refer to the "PROFINET System
Description (http://support.automation.siemens.com/WW/view/en/19292127)" system
manual.
Requirements
• Interface Module IM 153-4 PN
• up to IM 153-4AA00-0XB0: SIMATIC Micro Memory Card 64k and higher
• The programming device must be online on PROFINET to the IO device to let you assign a
device name to the interface module.
• The IO device is configured in HW Config and assigned an IP address.
96
Operating Instructions, 04/2022, EWA-4NEB7806006-09