Commissioning
6.1 PROFIBUS DP
• Only for DP interface FOC:
If the DP slave is located at the end of an FOC line, then the unused FOC interface must be
closed with a dummy plug.
• DP slave configured (refer to the online help / manual on configuration software)
Note
when configuring with GSD file
When using an IM 153-2BA81 (outdoor) you must convert the user parameter "MLFB" to
6ES7153-2BA81-0XB0.
If you configure the ET 200M (IM 153-2BAx2) with a GSD file, the length of the parameter
assignment message frame (maximum 244 bytes) can lead to limitations in the number of
assignable modules.
• Supply voltage for DP master switched on (refer to the DP master manual)
• Configuration loaded into the DP master (refer to the online help / manual on
configuration software)
• DP master switched to RUN (refer to the DP master manual)
Commissioning the DP slave
Commission the DP slave as follows:
1. Switch on the supply voltage for the DP slave.
2. If necessary, switch on the supply voltage for the load.
88
Operating Instructions, 04/2022, EWA-4NEB7806006-09
ET 200M