Connecting The Fiber-Optic Cable To The Im 153-2 Fo - Siemens SIMATIC ET 200M Operating Instructions Manual

Distributed i/o device
Hide thumbs Also See for SIMATIC ET 200M:
Table of Contents

Advertisement

Of course you can also continue to use the conventional bus connector with screw clamp
connection:
• up to 12 MBaud, with vertical cable departure
– without PD jack (6ES7972-0BA12-0XA0)
– with PD jack (6ES7972-0BB12-0XA0)
• up to 12 MBaud, with diagonal cable departure
– without PD jack (6ES7972-0BA41-0XA0)
– with PD jack (6ES7972-0BB41-0XA0)
Connecting the Bus Connector
Proceed as follows to connect the bus connector:
1. Plug the bus connector into the IM 153-x.
2. Tightly screw the bus connector into the IM 153-x.
3. If the bus connector is located at the start or end of a segment, you must connect the
terminating resistor (switch setting "ON").
Alternative: You use the PROFIBUS terminator as an active bus connector.
4. Lay the bus cable(s) in the area intended for the IM 153-x to the right alongside the DC 24 V
connection terminal.
Ensure that the nodes to which the terminating resistor is connected are always supplied with
voltage during power-up and operation.
5.2.2

Connecting the Fiber-Optic Cable to the IM 153-2 FO

Required accessories
• Packaging with Simplex connectors and polishing sets (6GK1901-0FB00-0AA0)
• Packaging with plug adapters (6ES7195-1BE00-0XA0)
• Tool for removing the cable sheath (6GK1905-6PA10)
ET 200M
Operating Instructions, 04/2022, EWA-4NEB7806006-09
Connecting
5.2 Connecting PROFIBUS DP
71