Channel-specific error messages
Table 9- 8
Error type of the channel-related diagnosis in accordance with the PROFIBUS standard
Error type
Error text
00000
0
reserved
B
D
00001
1
Short circuit
B
D
00010
2
Low voltage
B
D
00011
3
Overvoltage
B
D
00100
4
Overload
B
D
00101
5
Excess tempera-
B
D
ture
00110
6
Wire break
B
D
00111
7
High limit ex-
B
D
ceeded
01000
8
Low Limit ex-
B
D
ceeded
01001
9
Fault
B
D
01010
10
reserved
B
D
to
to
01111
15
B
D
ET 200M
Operating Instructions, 04/2022, EWA-4NEB7806006-09
Meaning
Short circuit, e.g.:
•
Sensor lines short circuited in accordance with P potential
•
Sensor lines short circuited in accordance with M poten-
tial
•
Output lines short circuited in accordance with P poten-
tial
•
Output lines short circuited in accordance with M poten-
tial
•
Output lines short circuited in accordance with ground
Supply voltage is below the tolerance range
Supply voltage is above the tolerance range
the output stage is overloaded
the output stage is overloaded and has become too hot
Wire break, e.g.:
•
Signal line to a sensor interrupted
•
Signal line from an actuator interrupted
•
Sensor power line interrupted
Value is above the over range
Value is below the under range
Error, e.g.:
•
Load voltage on output
•
Encoder supply
•
Hardware error in the module
•
Shield welded on or jammed
•
Life span of the switching element reached
Interrupt, error and system messages
9.1 PROFIBUS DP
Remedy
Correction of the pro-
cess wiring, M circuit, P
circuit
Correction on the
power supply, HART:
analog output current
established
Correction on the
power supply
Correction tuning of
module / actuator,
HART: analog output
saturated
Correction tuning of
module / actuator
Correction of the pro-
cess wiring
Correction tuning of
module / actuator
Correction tuning of
module / actuator
Exchange the module