Time Stamping Outside Of S7-400; Prerequisites - Siemens SIMATIC ET 200M Operating Instructions Manual

Distributed i/o device
Hide thumbs Also See for SIMATIC ET 200M:
Table of Contents

Advertisement

8.2.4

Time stamping outside of S7-400

8.2.4.1

Prerequisites

With the interface module IM 153-2Bxx1, time stamping is also possible outside of an S7-400
automation system.
The above principles and rules apply - if complied with, precisions of up to 1 ms can be
achieved.
Synchronization interval for the time: 10 s
Demands on the ET 200M and DP master
ET 200M:
• IM 153-2 as of order number 6ES7153-2Bxx1-0XB0
• suitable DI modules
• IM 153-2 must be configured via GSD rev. 5 (e.g. enabling of interrupts)
• for IM 153-2 the DPV1 mode must be activated
• Synchronization interval in accordance with the setting on the clock master
DP master:
• must fulfill requirements in accordance with DPV1
• must be able to process interrupts
• must be able to process data records (read / write)
• must be able to send / forward time message frames or a clock master must be available in
the same PROFIBUS DP line
ET 200M
Operating Instructions, 04/2022, EWA-4NEB7806006-09
8.2 Time stamping the input signals with IM 153-2
Functions
141