Replacing The Bus Module - Siemens SIMATIC ET 200M Operating Instructions Manual

Distributed i/o device
Hide thumbs Also See for SIMATIC ET 200M:
Table of Contents

Advertisement

Maintenance and service

7.8 Replacing the bus module

7.8
Replacing the bus module
Removing the bus module
Only remove bus modules if they are de-energized!
Proceed as follows when removing the bus module:
1. With the on / off switch of the power supply module to 0
(
2. Remove the modules on the bus module that is to be replaced, on all the bus modules on
the right, as well as the module directly to the left.
3. The bus modules are locked together. On the bus module that is to be replaced, press down
the lock of the bus module on the right, and push the bus module(s) on the right to the
right.
4. On the bus module on the left, press down the lock of the bus module that is to be replaced
and push this one to the right.
5. Using a screwdriver push the lock down towards the rail.
6. Lift the bus module off the rail. You can also pull the bus module out from the right side of
the rail.
Installing a New Bus Module
You fit the new bus module as described in chapter "Installing Active Bus Modules and
Modules (Configuration with Active Bus Modules) (Page 65)".
114
: output voltages 0 V).
Lock holding the bus modules together
Lock holding the module to the rail
Operating Instructions, 04/2022, EWA-4NEB7806006-09